Skip to content
Exclusive agent of MECH products in Saudi Arabia
Store Request a quote

MECH MECHANICAL JOINT DRY BARREL FIRE HYDRANT UL/FM MODEL SSF-J

National Water Company logo
Approved by the National Water Company Dry fire hydrants — sizes 100 – 150 mm · Certificate 2026-37271-02 · valid to Nov 2028
View certificate

Model SSF-J

Design standard
AWWA C502
Connection ends
Mechanical joint ANSI/AWWA C111/A21.11
Nozzle threads
NFPA 1963
Working pressure
300 PSI (200 / 250 PSI on request)
Temperature
4 – 60 °C
Coating
FBE — ANSI/AWWA C550
Approvals
UL 246 / FM 1510 / NSF/ANSI 61
Outlets
2 × 2-1/2" hose + 1 × 4-1/2" pumper
Request a quote for this product
Or buy from the online store
SIZES & DIMENSIONS

Sizes & dimensions

SizeDNBase valve sizeA (mm)B (mm)C (mm)E (mm)F (mm)F1 (mm)F2 (mm)D1 (mm)D2 (mm)D3 (mm)N-ΦAN-ΦBG1G2
6"DN1505-1/4" (128 mm)846460761524309.4210.6350.6206.2177.8241.36-Φ22.32-Φ231-4.5"1-2.5"
PROJECT APPROVALS

Approved on projects

11 projects and 10 owners approved this product or its family through the project consultants.

Original approval letters are provided on request with your submittal.

The MECH mechanical joint dry barrel fire hydrant ul/fm, model SSF-J, working pressure 300 PSI (200 / 250 PSI on request), UL 246 / FM 1510 / NSF/ANSI 61 approved. An outdoor fire hydrant fed from the underground main, with two hose outlets and a large pumper outlet. This guide explains what it does and how it works, related models, technical data, the critical point in selection and installation, and common mistakes.

At a glance

  • A fire hydrant is an outdoor water supply point for fire crews, installed on the underground main.
  • Working pressure 300 PSI (200 / 250 PSI on request).
  • Approvals: UL 246 / FM 1510 / NSF/ANSI 61.
  • Connection: Mechanical joint ANSI/AWWA C111/A21.11.
  • Operating temperature: 4 – 60 °C.

Fire hydrant: what it does and how it works

A fire hydrant is an outdoor water supply point for fire crews, installed on the underground main. Per the product data it has two 2-1/2″ hose outlets and one 4-1/2″ pumper outlet, with outlet threads to NFPA 1963.

A wet-barrel hydrant is always full of water with a valve on each outlet; a dry-barrel hydrant has its main valve below ground, so the barrel drains after closing.

Related models

fire hydrant family
ModelProductSizesPressureApprovals
SSZ2WET BARREL FIRE HYDRANT UL/FM RED—300 PSIUL 246 / FM 1511 / NSF/ANSI 61
SSF-J — this productMECHANICAL JOINT DRY BARREL FIRE HYDRANT UL/FM—300 PSIUL 246 / FM 1510 / NSF/ANSI 61
SSFDRY FIRE HYDRANT6″ (DN150)300 PSIUL 246 / FM 1510

Technical data

Specification of model SSF-J
ItemSpecification
Design standardAWWA C502
Connection endsMechanical joint ANSI/AWWA C111/A21.11
Nozzle threadsNFPA 1963
Working pressure300 PSI (200 / 250 PSI on request)
Temperature4 – 60 °C
CoatingFBE — ANSI/AWWA C550
ApprovalsUL 246 / FM 1510 / NSF/ANSI 61
Outlets2 × 2-1/2″ hose + 1 × 4-1/2″ pumper

Dimensions for every size are in the size table at the top of the page.

Wet or dry barrel?

A dry-barrel hydrant (AWWA C502) drains its barrel after closing, used where freezing or damage is a concern; a wet-barrel hydrant (AWWA C503) is simpler with each outlet independent. The designer selects the type per the project specification and the authority having jurisdiction.

Caution

Outlet threads must match the local fire department couplings; confirm the required thread before ordering.

Installation steps

  1. Install on a branch from the underground main with an isolating valve per the project details.
  2. Seat the base on a concrete thrust block; for a dry hydrant leave gravel around the base for drainage.
  3. Face the pumper outlet toward the road and keep clear space around the hydrant.
  4. Flush and pressure / flow test the hydrant after installation.

Common mistakes

  • Outlet threads that do not match fire department couplings.
  • No thrust block, or no drainage at a dry hydrant base.
  • Placing the hydrant where fire trucks cannot reach it.

Files and ordering

On this page: Product page (catalogue), Installation & operation manual, MECH Fire Protection Valves Catalogue (UL/FM), Material Safety Data Sheet (MSDS). Add the product to your request list with size and quantity and we send a quotation, or build a submittal PDF for the consultant. Fu-Mech is the exclusive MECH agent in Saudi Arabia.

Frequently asked questions

How many outlets does it have?

Two 2-1/2″ hose outlets and one 4-1/2″ pumper outlet, per the product data.

Is it suitable for potable water?

Some models carry NSF/ANSI 61 as shown in their approvals; check the model you need.

What is the working pressure of model SSF-J?

300 PSI (200 / 250 PSI on request) per the product data. The pressure for each size or listed model is in the size table and datasheet.

What approvals does it carry?

UL 246 / FM 1510 / NSF/ANSI 61 per the product data. Check the size and listed model in the approval listings, and see how to verify UL and FM approvals.

What end connection does it have?

Mechanical joint ANSI/AWWA C111/A21.11. Choose the connection that matches the adjacent pipe and fittings.

References

  • AWWA C502 — Dry-Barrel Fire Hydrants
  • NFPA 1963 — Standard for Fire Hose Connections
  • NSF/ANSI 61 — Drinking Water System Components — Health Effects
  • AWWA C550 — Protective Interior Coatings for Valves and Hydrants
  • AWWA C111 — Rubber-Gasket Joints for Ductile-Iron Pressure Pipe and Fittings
  • UL 246 — Hydrants for Fire-Protection Service
  • MECH catalogue — Fire fighting valves

This guide is general information to help with selection. Figures come from the product data on this page and the MECH catalogue; final design is by the project’s approved designer to the applicable standards and the project specification.