TYCO TY7236 Pendent Sprinkler, K16.8, 3/4″ NPT — ESFR-17

Model TY7236

Brand
TYCO
Model
TY7236
Series
ESFR-17
Orientation
Pendent
K-factor
16.8 gpm/psi½
Thread connection
3/4" NPT
Response
Early Suppression, Fast Response (ESFR)
Coverage
ESFR storage sprinkler
Temperature ratings
68 / 96 °C
Max. working pressure
175 psi (12.1 bar)
Approvals
UL · C-UL · FM
Datasheet
TFP322
Request a quote for this product
Or buy from the online store

The TYCO TY7236 is the pendent model of the ESFR-17 series, with a K 16.8 discharge coefficient and 3/4″ NPT thread, early suppression, fast response (esfr) and esfr storage sprinkler, operated by a glass bulb. It is designed for ceiling-only protection of high-piled storage without in-rack sprinklers, for most common materials, cartoned and uncartoned plastics and some tire and roll paper arrangements. Installed hanging below the pipe with the deflector facing down. For where the sprinkler sits in the whole system, see the complete guide to sprinkler systems in Saudi Arabia.

In short

  • Model (SIN): TY7236 — Pendent.
  • Discharge coefficient K 16.8, 3/4″ NPT connection.
  • Glass bulb, early suppression, fast response (esfr).
  • Temperature ratings in the datasheet: 68 / 96 °C.
  • Maximum working pressure: 175 psi (12.1 bar).
  • Series approvals: UL, C-UL, FM. The approval of each model, finish and rating is in the approvals table of datasheet TFP322.

How this sprinkler works

The glass bulb contains a fluid that expands when exposed to heat. When the rated temperature is reached, the fluid expands enough to shatter the bulb, the sprinkler opens and the deflector spreads the water over the fire area.

Installed hanging below the pipe with the deflector facing down. An ESFR sprinkler works in suppression mode: a large volume of water with strong droplets early on, to suppress the fire rather than only control it.

Models in the series

Models in datasheet TFP322
SINOrientationK-factorThread
TY7236 — this modelPendent16.83/4″ NPT

Links to the other models are in the “Similar models” table below. The choice of model comes from the hydraulic calculation, hazard classification and installation method in the project design.

Application notes

  • Coverage 64 – 100 ft² (5.8 – 9.3 m²); maximum spacing 12 ft (3.7 m) for buildings up to 30 ft and 10 ft (3.1 m) above; minimum spacing 8 ft (2.4 m); clearance to commodity 36 in.

Technical data

Technical data — TY7236 per TYCO datasheet TFP322
ItemValue
Model (SIN)TY7236
OrientationPendent
Discharge coefficientK 16.8 gpm/psi½ (241.9 L/min/bar½)
Thread3/4″ NPT
Element and responseGlass bulb — Early Suppression, Fast Response (ESFR)
CoverageESFR storage sprinkler
Temperature ratings68 / 96 °C
Maximum working pressure175 psi (12.1 bar)
Installation torque10 – 20 lb-ft (13.4 – 26.8 N·m)
WrenchW-Type 35
ApprovalsUL, C-UL, FM
DatasheetTYCO TFP322

The critical point: bulb protector and wrench

Do not remove the bulb protector until the sprinkler is placed in service. The W-Type 35 wrench must be used; torque 10 – 20 lb-ft, or hand-tight plus 1-1/4 to 1-1/2 turns of the wrench.

Installation steps

  1. Inspect before installing: never install a sprinkler whose bulb is cracked or has lost liquid.
  2. Install the sprinkler in its correct orientation (Pendent) as shown in the datasheet — never reversed.
  3. Apply pipe-thread sealant to the threads, then hand-tighten the sprinkler.
  4. Finish with the specified wrench (W-Type 35) within 10 – 20 lb-ft (13.4 – 26.8 N·m). Higher torque can distort the inlet and cause leakage.

Common mistakes

  • Installing a sprinkler that was dropped, struck or slipped by the wrench. The datasheet requires any such sprinkler to be replaced.
  • Painting or coating sprinklers on site. Sprinklers must not be altered after leaving the factory; altered sprinklers are replaced.
  • Hanging objects from sprinklers, or cleaning them with anything other than a gentle feather duster.

Maintenance

Sprinklers that leak or show visible corrosion must be replaced, as must sprinklers exposed to corrosive products of combustion that cannot be fully cleaned. The owner is responsible for inspection, testing and maintenance to NFPA 25 and the authority having jurisdiction, preferably by a qualified inspection service. Before closing a main control valve for maintenance, obtain permission from the proper authorities and notify everyone affected.

Files and ordering

TYCO datasheet TFP322 and the available approval certificates are in the files section of this page. When ordering, state the model TY7236, temperature rating and finish. The datasheet lists the part numbers (P/N) for each combination.

How to order

Use the “Build your order” section on this page: add every model and quantity, then send the whole order by email or WhatsApp. It reaches us as a tidy PDF request sheet and we contact you with the quotation.

FAQ

What does TY7236 mean?

It is TYCO’s Sprinkler Identification Number (SIN). It identifies the exact model — orientation, K-factor and thread. The sprinkler is ordered by this number together with temperature rating and finish.

How do I choose the temperature rating?

From the highest expected ceiling temperature and the rating classes in the project’s governing standard, within the ratings available for this model in the datasheet.

Do all models in the series carry the same approvals?

Not always. The approvals table in datasheet TFP322 gives each model’s approvals by rating and finish, so check it when the project requires a specific approval.

Does the warehouse need in-rack sprinklers?

ESFR sprinklers are for ceiling-only protection in the applications given in the datasheet and governing standard (NFPA or FM Global), removing the need for in-rack sprinklers within those conditions.

References

  • TYCO TFP322 — Series datasheet (attached)
  • NFPA 13 — Standard for the Installation of Sprinkler Systems
  • NFPA 25 — Inspection, Testing and Maintenance of Water-Based Fire Protection Systems
  • TYCO TFP700 — Installer warning for handling and installing sprinklers

This page is general information to help with selection and ordering, taken from the attached TYCO datasheet. Final design is set by the project’s approved designer; the project specification, the consultant’s drawings and the latest datasheet revision govern.