TYCO CHEC TY4332 Concealed Horizontal Sidewall Sprinkler — Quick Response, K8.0 (TFP265)

Model TY4332

Brand
TYCO
Series
CHEC
Models
TY4332
Orientation
Concealed Horizontal Sidewall
K-factor
8.0 gpm/psi½
Thread connection
3/4" NPT
Response
Quick Response
Coverage
Extended Coverage
Temperature ratings
68°C sprinkler with 59°C cover plate
Max. working pressure
175 psi (12.1 bar)
Approvals
UL · C-UL · NYC
Datasheet
TFP265
Request a quote for this product
Or buy from the online store

TYCO Series CHEC (datasheet TFP265) are concealed horizontal sidewall sprinklers with a K 8.0 discharge coefficient, quick response and extended coverage, operated by a glass bulb 3 mm. They are designed for architecturally sensitive light hazard areas such as hotel rooms, dormitories, offices and hospitals, with extended coverage. The series has 1 models; each has a Sprinkler Identification Number (SIN) that fixes its orientation, K-factor and thread, and the sprinkler is ordered by that number. The models table at the top of this page lists them all; for where the sprinkler sits in the whole system, see the complete guide to sprinkler systems in Saudi Arabia.

In short

  • Models: TY4332.
  • Orientations: Concealed Horizontal Sidewall.
  • K-factor: K 8.0; thread: 3/4″ NPT.
  • Glass bulb 3 mm, quick response.
  • Temperature ratings: 68°C sprinkler with 59°C cover plate.
  • Maximum working pressure: 175 psi (12.1 bar).
  • Series approvals: UL, C-UL, NYC. The approval of each model, finish and rating is in the approvals table of datasheet TFP265.

How this sprinkler works

The glass bulb contains a fluid that expands when exposed to heat. When the rated temperature is reached, the fluid expands enough to shatter the bulb, the sprinkler opens and the deflector spreads the water over the fire area.

In a concealed sprinkler the flat cover plate is soldered to the retainer at three points with a solder rated lower than the sprinkler. Fire heat first drops the cover plate, the deflector drops on its guide pins to the operating position, then the sprinkler operates at its own rating.

Concealed Horizontal Sidewall: Installed within the wall with only a flat cover plate visible.

Quick response means the thermal element reacts faster, so the sprinkler operates earlier than a standard-response sprinkler of the same rating.

How to choose the model

  • Orientation: Concealed Horizontal Sidewall — Installed within the wall with only a flat cover plate visible.
  • K-factor: K 8.0 for every model in the series.
  • Thread: usually follows the K-factor, and must match the fitting on the system.
  • Temperature rating and finish: stated with the order for each model, from the highest expected ceiling temperature and the environment.

Application notes

  • A two-piece push-on, thread-off cover design; minimum lateral spacing along a wall and flow requirements are in the datasheet table.

Technical data

Technical data for Series CHEC per TYCO datasheet TFP265
ItemValue
Models (SIN)TY4332
OrientationsConcealed Horizontal Sidewall
Discharge coefficientK 8.0 (115.2 L/min/bar½)
Thread3/4″ NPT
ElementGlass bulb 3 mm
ResponseQuick Response
CoverageExtended Coverage
Temperature ratings68°C sprinkler with 59°C cover plate
Maximum working pressure175 psi (12.1 bar)
Installation torque10 – 20 lb-ft (13.4 – 26.8 N·m)
WrenchW-Type 7
ApprovalsUL, C-UL, NYC
DatasheetTYCO TFP265

The critical point: centreline and cover

Install with its centreline perpendicular to the back wall and parallel to the ceiling, tighten with the W-Type 7 wrench at 10 – 20 lb-ft, and use only factory-finished CHEC cover plates.

Installation steps

  1. Inspect before installing: never install a sprinkler whose bulb is cracked or has lost liquid.
  2. Install each sprinkler in the correct orientation for its model, as shown in the datasheet — never reversed.
  3. Apply pipe-thread sealant to the threads, then hand-tighten the sprinkler.
  4. Finish with the specified wrench (W-Type 7) within the torque for the model’s thread: 10 – 20 lb-ft (13.4 – 26.8 N·m). Higher torque can distort the inlet and cause leakage.
  5. After the ceiling or wall is finished and the system pressure tested, fit the specified cover plate until its flange touches the surface — never painted.

Common mistakes

  • Repainting the cover plate or replacing it with an unspecified one. The sprinkler is listed only with its factory-finished cover plates.
  • Installing a sprinkler that was dropped, struck or slipped by the wrench. The datasheet requires any such sprinkler to be replaced.
  • Painting or coating sprinklers on site. Sprinklers must not be altered after leaving the factory; altered sprinklers are replaced.
  • Hanging objects from sprinklers, or cleaning them with anything other than a gentle feather duster.

Maintenance

Sprinklers that leak or show visible corrosion must be replaced, as must sprinklers exposed to corrosive products of combustion that cannot be fully cleaned. The owner is responsible for inspection, testing and maintenance to NFPA 25 and the authority having jurisdiction, preferably by a qualified inspection service. Before closing a main control valve for maintenance, obtain permission from the proper authorities and notify everyone affected.

Files and ordering

TYCO datasheet TFP265 and the available approval certificates are in the files section of this page. When ordering, state for each line the model (SIN), temperature rating and finish, cover plate. The datasheet lists the part numbers (P/N) for each combination.

How to order

Use the “Build your order” section on this page: add every model and quantity, then send the whole order by email or WhatsApp. It reaches us as a tidy PDF request sheet and we contact you with the quotation.

FAQ

What do model numbers such as TY4332 mean?

They are TYCO Sprinkler Identification Numbers (SIN). Each identifies an exact model — orientation, K-factor and thread. The sprinkler is ordered by this number together with temperature rating and finish.

How do I choose the temperature rating?

From the highest expected ceiling temperature and the rating classes in the project’s governing standard, within the ratings available for the model in the datasheet.

Do all models in the series carry the same approvals?

Not always. The approvals table in datasheet TFP265 gives each model’s approvals by rating and finish, so check it when the project requires a specific approval.

What is the benefit of quick response?

The thermal element reacts faster, so the sprinkler operates earlier and limits heat and smoke spread; standards require it in some occupancies such as light hazard.

When does the cover plate drop?

The plate is soldered with a lower-rated solder than the sprinkler, so it drops first in a fire; the deflector then drops and the sprinkler operates at its own rating.

References

  • TYCO TFP265 — Series datasheet (attached)
  • NFPA 13 — Standard for the Installation of Sprinkler Systems
  • NFPA 25 — Inspection, Testing and Maintenance of Water-Based Fire Protection Systems
  • TYCO TFP700 — Installer warning for handling and installing sprinklers

This page is general information to help with selection and ordering, taken from the attached TYCO datasheet. Final design is set by the project’s approved designer; the project specification, the consultant’s drawings and the latest datasheet revision govern.

Similar models

Same type — compare K-factor, response and approvals to pick the right one.

ProductModelKResponseApprovals
TYCO ILLUSION TY5521 Concealed Pendent Sprinkler — Quick Response, K11.2 (TFP184)TY552111.2Quick ResponseUL · C-UL
TYCO RFII ECLH TY3532 Concealed Pendent Sprinkler — Quick Response, K5.6 (TFP260)TY35325.6Quick ResponseUL · C-UL · NYC
TYCO RFII HSW TY3521 Concealed Horizontal Sidewall Sprinkler — Quick Response, K5.6 (TFP185)TY35215.6Quick ResponseUL · C-UL · FM (standard response only)
TYCO RFIII ECLH TY4522 Concealed Horizontal Sidewall Sprinkler — Quick Response, K8.0 (TFP270)TY45228.0Quick ResponseUL · C-UL · EAC
TYCO Series RFII Royal Flush II Sprinklers — Quick / Standard Response, K5.6 (TFP181)TY3531, TY35515.6Quick or standard response, per listing and installationUL · C-UL · FM · LPCB · VdS · NYC (per datasheet)