EATON EFM-APS200 UL Addressable Dual Action Pull Station

Model EFM-APS200

Brand
EATON
Models
EFM-APS200
Type
Addressable — Dual Action
Construction
Die-cast metal, red
Dimensions
118 × 80 × 80 mm
Includes
ULMCIM-C
Request a quote for this product
Or buy from the online store
Certificates & approvals

Ask us for this product's certificates.

The EATON EFM-APS200 is a addressable dual action fire alarm pull station from the Eaton UL range, in red die-cast metal with raised white lettering. It comes with the ULMCIM-C fast-response input module, so no hard addressing is needed.

In short

  • Dual Action: the push bar rotates inward and the handle is pulled in one motion.
  • Key reset; corrosion-resistant gold-plated SPST contacts.
  • The handle locks after pulling and is visible from 50 ft.
  • Flush on a single-gang box, or surface on an SGB32S or SGWP back box.

How the pull station works

Pulling the white handle fully down locks it in place and the module signals the panel with its own address. Reset by opening the station with the key, returning the handle upright and relocking.

Models in the datasheet

Pull stations in the datasheet
ModelDescription
EFM-APS100Addressable — Single Action
EFM-APS100WPAddressable — Single Action, Weatherproof
EFM-APS200 — this modelAddressable — Dual Action
EFM-APS200WPAddressable — Dual Action, Weatherproof
SG42BK2Conventional — Conventional Single Action
SG42BK1Conventional — Conventional Dual Action

Links to the other models are in the “Similar models” table below.

Technical data

Technical data — per EATON datasheet APS
ItemValue
ModelEFM-APS200
TypeAddressable — Dual Action
ConstructionRed die-cast metal
Dimensions118 × 80 × 80 mm
RatingIndoor
SLCClass A, Style 7
ApprovalUL listed

The critical point: correct wiring

Field wiring connects to the clamping terminals on the ULMCIM-C, not wrapped around terminal screws, and the module is programmed as a pull station in Site Installer.

General notes on pull stations

  • Location: a pull station within 5 ft (1.5 m) of each exit door on every floor, per NFPA 72.
  • Height: the operable part between 42 and 48 in (1.07 – 1.22 m) above the floor.
  • Travel distance: no more than 200 ft (61 m) to the nearest station on a floor.
  • Where tampering is likely, listed protective covers are added; outdoor stations use weatherproof models.

General engineering notes

These points are general principles from NFPA 72 and common design practice, not from the EATON datasheet. The final decision rests with the project’s approved designer per the adopted edition of the standard and the authority having jurisdiction.

Installation steps

  1. Fit the box: a single-gang box for flush, or SGB32S / SGWP for surface (four 0.187″ holes).
  2. Open the station with the key and fix the mounting plate to the box with the supplied screws.
  3. Wire per the wiring diagram and check the handle is in standby before locking.
  4. Test the alarm, then reset with the key.

Common mistakes

  • Wrapping wires around terminal screws instead of the clamping terminals.
  • Installing an indoor station outdoors instead of a WP model.
  • Do not use high-voltage insulation testers while devices or the panel are connected, as the Eaton datasheets warn.

Inspection and maintenance

Before any test or maintenance, notify the owner, the monitoring station and everyone affected, as testing may operate alarms or linked outputs. The owner is responsible for inspection, testing and maintenance per NFPA 72 and the authority having jurisdiction, preferably by a qualified company.

Files and ordering

The EATON datasheet (APS) and the available UL certificate are in the files section of this page. When ordering, state the model EFM-APS200.

How to order

Use the “Build your order” section on this page: add every model and quantity, then send the whole order by email or WhatsApp. It reaches us as a tidy PDF request sheet and we contact you with the quotation.

FAQ

Single vs dual action?

Single action is a pull only; dual action needs a push then a pull, reducing accidental operation.

Does it need addressing?

No, the ULMCIM-C is soft addressed.

References

  • EATON APS — Datasheet (attached)
  • NFPA 72 — National Fire Alarm and Signaling Code

This page is general information to help with selection and ordering, taken from the attached EATON datasheet. Final design is set by the project’s approved designer; the project specification, the consultant’s drawings and the latest datasheet revision govern.