TYCO TY3311 Horizontal Sidewall Sprinkler, K5.6, 1/2″ NPT — TY-L

Model TY3311

Brand
TYCO
Model
TY3311
Series
TY-L
Orientation
Horizontal Sidewall
K-factor
5.6 gpm/psi½
Thread connection
1/2" NPT
Response
Standard Response
Coverage
Standard Coverage
Temperature ratings
74 / 100 / 138 °C
Max. working pressure
175 psi (12.1 bar)
Approvals
UL · C-UL · FM
Datasheet
TFP120
Request a quote for this product
Or buy from the online store

The TYCO TY3311 is the horizontal sidewall model of the TY-L series, with a K 5.6 discharge coefficient and 1/2″ NPT thread, standard response and standard coverage, operated by a solder-type element. It is designed for light and ordinary hazard commercial occupancies such as banks, hotels, shopping malls and offices. Installed along a wall or the side of a beam just below the ceiling, throwing water horizontally into the room. For where the sprinkler sits in the whole system, see the complete guide to sprinkler systems in Saudi Arabia.

In short

  • Model (SIN): TY3311 — Horizontal Sidewall.
  • Discharge coefficient K 5.6, 1/2″ NPT connection.
  • Solder-type element, standard response.
  • Temperature ratings in the datasheet: 74 / 100 / 138 °C.
  • Maximum working pressure: 175 psi (12.1 bar).
  • Series approvals: UL, C-UL, FM. The approval of each model, finish and rating is in the approvals table of datasheet TFP120.

How this sprinkler works

A copper tube sealed by two stainless steel balls holds a fusible alloy. When the rated temperature is reached the alloy melts, the balls are forced toward each other and the tension mechanism releases, letting the sprinkler operate.

Installed along a wall or the side of a beam just below the ceiling, throwing water horizontally into the room. Standard response is typically used for storage and industrial areas, per the project design.

Models in the series

Models in datasheet TFP120
SINOrientationK-factorThread
TY3311 — this modelHorizontal Sidewall5.61/2″ NPT

Links to the other models are in the “Similar models” table below. The choice of model comes from the hydraulic calculation, hazard classification and installation method in the project design.

Application notes

  • Sidewall sprinklers are used instead of pendents or uprights for aesthetic or construction reasons where piping across the ceiling is not wanted.
  • Wax-coated sprinklers are tightened with an adjustable wrench taking care not to damage the wax; retouching with a heated rod is permitted only at initial installation.

Technical data

Technical data — TY3311 per TYCO datasheet TFP120
ItemValue
Model (SIN)TY3311
OrientationHorizontal Sidewall
Discharge coefficientK 5.6 gpm/psi½ (80.6 L/min/bar½)
Thread1/2″ NPT
Element and responseSolder-type element — Standard Response
CoverageStandard Coverage
Temperature ratings74 / 100 / 138 °C
Maximum working pressure175 psi (12.1 bar)
Installation torque7 – 14 lb-ft (9.5 – 19.0 N·m)
WrenchW-Type 9
ApprovalsUL, C-UL, FM
DatasheetTYCO TFP120

The critical point: wrench and ceiling temperature

Tighten with the W-Type 9 wrench at 7 – 14 lb-ft. A wax-coated 138°C sprinkler is limited to a 65°C ceiling temperature, like the 100°C rating.

Installation steps

  1. Install the sprinkler in its correct orientation (Horizontal Sidewall) as shown in the datasheet — never reversed.
  2. Apply pipe-thread sealant to the threads, then hand-tighten the sprinkler.
  3. Finish with the specified wrench (W-Type 9) within 7 – 14 lb-ft (9.5 – 19.0 N·m). Higher torque can distort the inlet and cause leakage.

Common mistakes

  • Installing a sprinkler that was dropped, struck or slipped by the wrench. The datasheet requires any such sprinkler to be replaced.
  • Painting or coating sprinklers on site. Sprinklers must not be altered after leaving the factory; altered sprinklers are replaced.
  • Hanging objects from sprinklers, or cleaning them with anything other than a gentle feather duster.

Maintenance

Sprinklers that leak or show visible corrosion must be replaced, as must sprinklers exposed to corrosive products of combustion that cannot be fully cleaned. The owner is responsible for inspection, testing and maintenance to NFPA 25 and the authority having jurisdiction, preferably by a qualified inspection service. Before closing a main control valve for maintenance, obtain permission from the proper authorities and notify everyone affected.

Files and ordering

TYCO datasheet TFP120 and the available approval certificates are in the files section of this page. When ordering, state the model TY3311, temperature rating and finish. The datasheet lists the part numbers (P/N) for each combination.

How to order

Use the “Build your order” section on this page: add every model and quantity, then send the whole order by email or WhatsApp. It reaches us as a tidy PDF request sheet and we contact you with the quotation.

FAQ

What does TY3311 mean?

It is TYCO’s Sprinkler Identification Number (SIN). It identifies the exact model — orientation, K-factor and thread. The sprinkler is ordered by this number together with temperature rating and finish.

How do I choose the temperature rating?

From the highest expected ceiling temperature and the rating classes in the project’s governing standard, within the ratings available for this model in the datasheet.

Do all models in the series carry the same approvals?

Not always. The approvals table in datasheet TFP120 gives each model’s approvals by rating and finish, so check it when the project requires a specific approval.

References

  • TYCO TFP120 — Series datasheet (attached)
  • NFPA 13 — Standard for the Installation of Sprinkler Systems
  • NFPA 25 — Inspection, Testing and Maintenance of Water-Based Fire Protection Systems
  • TYCO TFP700 — Installer warning for handling and installing sprinklers

This page is general information to help with selection and ordering, taken from the attached TYCO datasheet. Final design is set by the project’s approved designer; the project specification, the consultant’s drawings and the latest datasheet revision govern.

Similar models

Same type — compare K-factor, response and approvals to pick the right one.

ProductModelKResponseApprovals
TYCO TY3331 Horizontal Sidewall Sprinkler, K5.6, 1/2″ NPT — TY-FRB5.6Quick ResponseUL · C-UL · FM · LPCB · NYC (per Table A)
TYCO TY3332 Horizontal Sidewall Sprinkler, K5.6, 1/2″ NPT — TY-FRB EC5.6Quick or standard response, per listing and installationUL · C-UL · FM · NYC (per Table A)
TYCO TY3351 Horizontal Sidewall Sprinkler, K5.6, 1/2″ NPT — TY-B5.6Standard ResponseUL · C-UL · FM · LPCB · NYC (per Table A)
TYCO TY3431 Vertical Sidewall Sprinkler, K5.6, 1/2″ NPT — TY-FRB5.6Quick ResponseUL · C-UL · FM · LPCB · NYC (per Table A)
TYCO TY3451 Vertical Sidewall Sprinkler, K5.6, 1/2″ NPT — TY-B5.6Standard ResponseUL · C-UL · FM · LPCB · NYC (per Table A)
TYCO TY4332 Horizontal Sidewall Sprinkler, K8.0, 3/4″ NPT — TY-FRB EC8.0Quick or standard response, per listing and installationUL · C-UL · FM · NYC (per Table A)