MECH GATE VALVE NRS MECHANICAL JOINT WITH POST FLANGE UL/FM RED MODEL Z35XC-2

Model Z35XC-2

Connection ends
Mechanical joint ANSI/AWWA C111/A21.11
Working pressure
300 PSI (200 / 250 PSI on request)
Temperature
4 – 60 °C
Coating
FBE — ANSI/AWWA C550
Approvals
UL / FM
Sizes
4" – 12" (DN100 – DN300)
Request a quote for this product
Or buy from the online store
SIZES & DIMENSIONS

Sizes & dimensions

SizeDNL Length (mm)H Height (mm)D (mm)D1 (mm)E (mm)F (mm)C (mm)n-ΦL Bolt holes
4"DN100229355232190.5152.9124.519.14-Φ22.2
6"DN150292448282241.3206.2177.819.16-Φ22.2
8"DN200318548340298.5260.9232.422.26-Φ22.2
10"DN250375626397355.6313.4284.423.88-Φ22.2
12"DN300378722454412.7366.7337.825.48-Φ22.2
PROJECT APPROVALS

Approved on projects

98 projects and 61 owners approved this product or its family through the project consultants.

and 86 more projects.

Original approval letters are provided on request with your submittal.

The MECH gate valve nrs mechanical joint with post flange ul/fm red, model Z35XC-2, sizes 4″ – 12″ (DN100 – DN300), working pressure 300 PSI (200 / 250 PSI on request), UL / FM approved. A non-rising-stem gate valve suited to limited space and buried mains. This guide explains what it does and how it works, related models, technical data, the critical point in selection and installation, and common mistakes. For more, read the guide OS&Y vs NRS gate valves.

At a glance

  • On an NRS (non-rising stem) gate valve the stem turns in place and the gate travels on it inside the body, so the valve height does not change on opening.
  • Sizes 4″ – 12″ (DN100 – DN300).
  • Working pressure 300 PSI (200 / 250 PSI on request).
  • Approvals: UL / FM.
  • Connection: Mechanical joint ANSI/AWWA C111/A21.11.
  • Operating temperature: 4 – 60 °C.

NRS gate valve: what it does and how it works

On an NRS (non-rising stem) gate valve the stem turns in place and the gate travels on it inside the body, so the valve height does not change on opening. It therefore suits limited headroom and buried mains.

Because the stem does not show position, an indicating device is used with it: an indicator post mounted on a flange on top of the valve showing “OPEN / SHUT”, or a stem cap operated with a key.

Related models

NRS gate valve family
ModelProductSizesPressureApprovals
Z85XC-2GATE VALVE NRS GROOVED WITH POST FLANGE UL RED4″ – 12″300 psigUL
Z55XGATE VALVE NRS FLANGE x GROOVE UL RED2-1/2″ – 12″300 psigUL
Z05XGATE VALVE NRS FLANGE x MECHANICAL JOINT UL RED3″ – 12″300 psigUL
Z35XGATE VALVE NRS MECHANICAL JOINT UL RED3″ – 12″300 psigUL
Z35XC-2 — this productGATE VALVE NRS MECHANICAL JOINT WITH POST FLANGE UL/FM RED4″ – 12″ (DN100 – DN300)300 PSIUL / FM
Z45XCGATE VALVE NRS FLANGED WITH STEM CAP UL/FM RED2″ – 24″ (DN50 – DN600)300 PSIUL / FM
Z85XGATE VALVE NRS GROOVED UL/FM RED2″ – 12″ (DN50 – DN300)300 PSIUL / FM
Z45XC-2GATE VALVE POST FLANGE UL/FM RED4″ – 24″ (DN100 – DN600)300 PSIUL / FM
Z45XGATE VALVE NRS H.WHEEL FLANGED UL/FM RED2″ – 12″ (DN50 – DN300)363 PSIUL / FM

Technical data

Specification of model Z35XC-2
ItemSpecification
Connection endsMechanical joint ANSI/AWWA C111/A21.11
Working pressure300 PSI (200 / 250 PSI on request)
Temperature4 – 60 °C
CoatingFBE — ANSI/AWWA C550
ApprovalsUL / FM
Sizes4″ – 12″ (DN100 – DN300)

Dimensions for every size are in the size table at the top of the page.

Showing the valve position

An NRS valve used as a fire-system control valve needs a means of showing its position, such as an indicator post on buried valves, or supervision per the standard. Choose the model with an indicator-post flange if the valve will be buried.

Caution

Indicator post height and extension rod length are set by the burial depth; send us the depth before ordering.

Installation steps

  1. Check the end type (flange, groove or mechanical joint) and its standard.
  2. Install with the stem vertical and upward, restraining mechanical joints with thrust blocks or restraints per the project details.
  3. For buried valves: fit the indicator post on the flange and set the OPEN/SHUT target to the actual position.
  4. Cycle fully open and shut and confirm the indicator matches.

Common mistakes

  • Burying the valve without an indicator post or other indication.
  • Not restraining mechanical joints against thrust.
  • An indicator that does not match the actual position after installation.

Files and ordering

On this page: Product datasheet, MECH Fire Protection Valves Catalogue (UL/FM), Material Safety Data Sheet (MSDS). Add the product to your request list with size and quantity and we send a quotation, or build a submittal PDF for the consultant. Fu-Mech is the exclusive MECH agent in Saudi Arabia.

Frequently asked questions

When should I choose NRS instead of OS&Y?

Where headroom is limited or the valve is buried in an underground main with an indicator post. See OS&Y vs NRS gate valves.

What is the indicator-post flange for?

It takes an indicator post (vertical or wall) so a buried valve can be operated from above ground and its position seen.

What is the working pressure of model Z35XC-2?

300 PSI (200 / 250 PSI on request) per the product data. The pressure for each size or listed model is in the size table and datasheet.

What approvals does it carry?

UL / FM per the product data. Check the size and listed model in the approval listings, and see how to verify UL and FM approvals.

What end connection does it have?

Mechanical joint ANSI/AWWA C111/A21.11. Choose the connection that matches the adjacent pipe and fittings.

References

  • AWWA C550 — Protective Interior Coatings for Valves and Hydrants
  • AWWA C111 — Rubber-Gasket Joints for Ductile-Iron Pressure Pipe and Fittings
  • MECH catalogue — Fire fighting valves

This guide is general information to help with selection. Figures come from the product data on this page and the MECH catalogue; final design is by the project’s approved designer to the applicable standards and the project specification.