Skip to content
Exclusive agent of MECH products in Saudi Arabia
Store Request a quote

MECH GROOVED ADAPTOR -MODEL 321GA

Model 321GA

Design standard
ASTM F1548, AWWA C606, ISO 6182-12
Material
Ductile iron ASTM A536 Gr. 65-45-12
Coating
Electrophoretic (std.) — epoxy / hot-dip galvanized optional
Sizes
2" – 24" (DN50 – DN600)
Request a quote for this product
Or buy from the online store
SIZES & DIMENSIONS

Sizes & dimensions

SizeDNPipe OD (mm)Max working pressure (PSI)L Length (mm)X (mm)Y (mm)Z (mm)Bolts / nuts (No.-Size)Certificate
2"DN5060.330065152120.5164-5/8UL / FM
2-1/2"DN6573.030065185139.7164-5/8—
3"DN8088.930065200152.4168-5/8—
4"DN100114.330070229190.5168-5/8UL / FM
6"DN150168.330070282241.3188-3/4—
8"DN200219.130075340298.5198-3/4UL / FM
10"DN250273.0300854063622112-7/8UL / FM
14"DN350355.6300127535476.33712-1—
16"DN400406.4300127595539.83716-1—
18"DN450457.2300140642577.84016-11/8—
20"DN500508.03001527006354320-11/8—
24"DN600609.6300152815749.34920-11/4—
PROJECT APPROVALS

Approved on projects

112 projects and 77 owners approved this product or its family through the project consultants.

and 100 more projects.

Original approval letters are provided on request with your submittal.

The MECH grooved adaptor, model 321GA, in ductile iron, sizes 2″ – 24″ (DN50 – DN600), working pressure up to 300 PSI, UL / FM approved depending on size. This guide explains what it does and how it works, compares it with related models, and covers technical data, the critical point in selection and installation, and common mistakes.

At a glance

  • A grooved flange (or flange adaptor) connects a grooved pipe to a flanged fitting, valve or pump without welding a flange on the pipe.
  • Sizes 2″ – 24″ (DN50 – DN600) — working pressure up to 300 PSI.
  • Approvals: UL / FM (vary by size).
  • Material Ductile iron ASTM A536 Gr. 65-45-12.
  • Designed to ASTM F1548, AWWA C606, ISO 6182-12.

What is a grooved flange and how does it work?

A grooved flange (or flange adaptor) connects a grooved pipe to a flanged fitting, valve or pump without welding a flange on the pipe. It locks onto the groove and then bolts to the mating flange.

It saves installation time and lets valves and equipment be removed easily for maintenance; it is the usual transition between a grooved network and flanged equipment.

Models in the same family

MECH grooved flange family
ModelItemSizesMax pressureApprovals
321MECH GROOVED FLANGE PN161-1/2″ – 24″300 PSIUL / FM / VdS / LPCB
321GMECH GROOVED ADAPTOR FLANGE PN161″ – 18″500 PSIUL / FM / VdS / LPCB
321GA — this productMECH GROOVED ADAPTOR2″ – 24″300 PSIUL / FM
321AMECH GROOVED FLANGES2″ – 24″300 PSIUL

Technical data

Model 321GA specification
ItemSpecification
Design standardASTM F1548, AWWA C606, ISO 6182-12
MaterialDuctile iron ASTM A536 Gr. 65-45-12
CoatingElectrophoretic (std.) — epoxy / hot-dip galvanized optional
Sizes2″ – 24″ (DN50 – DN600)
Approvals and pressure by size
ApprovalsSizesWorking pressure
UL / FM2″ – 10″300 PSI
Not stated in the table2-1/2″ – 24″300 PSI

Full dimensions for every size (bolts and more) are in the size table at the top of the page.

Matching the flange standard

The bolt holes must match the mating flange (for example PN16 or ANSI), and the mating flange face must suit the grooved flange gasket.

Caution

Check the drilling standard in the product table or catalogue before ordering, and confirm the mating flange face per MECH instructions.

Installation steps

  1. Check that the pipe ends are grooved to the right dimensions to AWWA C606 (roll or cut groove) and are free of burrs, rust and dirt.
  2. Inspect the gasket and lubricate its outside and lips with the lubricant recommended in the MECH catalogue; never use petroleum-based products with an EPDM gasket.
  3. Fit the gasket over one pipe end, bring the other end or the fitting into place, and slide the gasket so it is centred between the two grooves.
  4. Place both housing halves over the gasket so their keys engage the grooves on both sides.
  5. Hand-tighten the nuts first, making sure each oval-neck bolt sits in its hole, then tighten alternately and evenly to the torque in the MECH installation manual — never exceed it.

The fitting joins with grooved couplings; how the joint is finished (even pad gap or pads meeting) follows the coupling type in the MECH manual.

Full details and bolt torques are in the MECH installation manual among the files on this page.

Common mistakes

  • Letting the gasket lip overhang the pipe end or protrude into a groove, so the gasket is not centred on the joint.
  • Exceeding the specified bolt torque, which can damage the bolt or the joint.
  • Grooves that do not meet AWWA C606 dimensions, or pipe ends that are not square.
  • Tightening the nuts on one side only, so the housing tilts and the key does not seat in the groove.
  • Using petroleum-based lubricant that damages the EPDM gasket.

Files and ordering

On this page: Product page (catalogue), MECH Grooved Fittings & Couplings Catalogue, Installation & operation manual, Material Safety Data Sheet (MSDS). Add the product to your request list with size and quantity and we send a quotation, or build a submittal PDF for the consultant. Fu-Mech is the exclusive MECH agent in Saudi Arabia.

Frequently asked questions

Does it need welding?

No. It locks onto the pipe groove and bolts to the mating flange.

What is the maximum working pressure of model 321GA?

Up to 300 PSI. The pressure for each size is in the size table.

Is model 321GA UL / FM approved?

Yes. Approvals by size: UL / FM for 2″ – 10″; — for 2-1/2″ – 24″. See the size table on this page and the guide how to verify UL and FM approvals.

What is the gasket material, and does it suit all fluids?

Gasket type and suitable services are given in the MECH catalogue.

Does it suit roll-grooved and cut-grooved pipe?

Grooves are to AWWA C606, rolled or cut; what matters is correct groove dimensions. The difference is explained in the guide roll grooving vs cut grooving.

References

  • ASTM F1548 — Standard Specification for Performance of Fittings for Use with Gasketed Mechanical Couplings Used in Piping Applications
  • AWWA C606 — Grooved and Shouldered Joints
  • ISO 6182-12 — Fire protection — Automatic sprinkler systems — Requirements and test methods for grooved-end components for steel pipe systems
  • ASTM A536 — Standard Specification for Ductile Iron Castings
  • UL 213 — Rubber Gasketed Fittings for Fire-Protection Service
  • FM 1920 — Approval Standard for Pipe Couplings and Fittings for Fire Protection Systems
  • MECH catalogue — Grooved Fittings & Couplings — and installation manual

This guide is general information to help with selection. Figures come from the product data on this page and the MECH catalogue; final design is by the project’s approved designer to NFPA 13 and the project specification.