Model H44X2

Design standard
AWWA C508
Connection ends
Flange ASME B16.1 CL125
Working pressure
300 PSI
Temperature
0 – 80 °C
Coating
FBE — ANSI/AWWA C550
Sizes
2" – 12" (DN50 – DN300)
Request a quote for this product
Or buy from the online store
SIZES & DIMENSIONS

Sizes & dimensions

SizeDNL Standard AWWA C508 (mm)L Optional ASME B16.10 (mm)D Flange diameter (mm)D1 Bolt circle (mm)b Flange thickness (mm)n-Φd Bolt holesH Height (mm)
2"DN50203203152120.5164-Φ19.1133
2.5"DN65254216178139.517.54-Φ19.1150
3"DN80278241191152.5194-Φ19.1150
4"DN100330292229190.5248-Φ19.1218
6"DN150406356279241.525.58-Φ22.2290
8"DN200495495343298.528.58-Φ22.2330
10"DN25062262240636230.512-Φ25.4350
12"DN3006606984834323212-Φ25.4376
PROJECT APPROVALS

Approved on projects

17 projects and 11 owners approved this product or its family through the project consultants.

and 5 more projects.

Original approval letters are provided on request with your submittal.

The MECH swing check valve flanged blue, model H44X2, sizes 2″ – 12″ (DN50 – DN300), working pressure 300 PSI. A check valve for water networks. This guide explains what it does and how it works, related models, technical data, the critical point in selection and installation, and common mistakes. For more, read the guide check valves in fire protection.

At a glance

  • A check valve opens under flow in the right direction and closes automatically when flow stops or reverses, preventing backflow from the system to the supply or from one pump into another.
  • Sizes 2″ – 12″ (DN50 – DN300).
  • Working pressure 300 PSI.
  • Connection: Flange ASME B16.1 CL125.
  • Operating temperature: 0 – 80 °C.

Check valve: what it does and how it works

A check valve opens under flow in the right direction and closes automatically when flow stops or reverses, preventing backflow from the system to the supply or from one pump into another.

This model is for water, pumping and HVAC networks (blue).

Related models

check valve family
ModelProductSizesPressureApprovals
DH77XWAFER CHECK VALVE BLUE2″ – 18″ (DN50 – DN450)300 PSI—
H44X2 — this productSWING CHECK VALVE FLANGED BLUE2″ – 12″ (DN50 – DN300)300 PSI—

Technical data

Specification of model H44X2
ItemSpecification
Design standardAWWA C508
Connection endsFlange ASME B16.1 CL125
Working pressure300 PSI
Temperature0 – 80 °C
CoatingFBE — ANSI/AWWA C550
Sizes2″ – 12″ (DN50 – DN300)

Dimensions for every size are in the size table at the top of the page.

Direction and orientation

The arrow on the body must point with the flow, and the orientation (horizontal or vertical with upward flow) must be within what the model’s listing and datasheet allow.

Caution

Do not fit a check valve directly after an elbow or pump without the recommended straight run, as turbulence makes the clapper chatter and wear.

Installation steps

  1. Check the arrow points with the flow.
  2. Install in a listed orientation, with enough straight pipe upstream.
  3. For wafer type: make sure the disc moves freely within the adjacent flanges.
  4. Test closure after commissioning.

Common mistakes

  • Installing it against the flow.
  • Fitting it right after an elbow or pump so it chatters.
  • Vertical downward-flow installation that is not allowed.

Files and ordering

On this page: Product datasheet, MECH Water Valves Catalogue, Material Safety Data Sheet (MSDS). Add the product to your request list with size and quantity and we send a quotation, or build a submittal PDF for the consultant. Fu-Mech is the exclusive MECH agent in Saudi Arabia.

Frequently asked questions

What is the difference between swing and wafer types?

A swing check has a hinged clapper and is easy to inspect; a wafer check is slimmer and fits between two flanges. See check valves.

Where is it installed in a fire system?

On fire pump discharges, the fire department connection and network supplies, per the design.

What is the working pressure of model H44X2?

300 PSI per the product data. The pressure for each size or listed model is in the size table and datasheet.

What end connection does it have?

Flange ASME B16.1 CL125. Choose the connection that matches the adjacent pipe and fittings.

References

  • ASME B16.1 — Gray Iron Pipe Flanges and Flanged Fittings
  • AWWA C550 — Protective Interior Coatings for Valves and Hydrants
  • AWWA C508 — Swing-Check Valves for Waterworks Service
  • MECH catalogue — Fire fighting valves

This guide is general information to help with selection. Figures come from the product data on this page and the MECH catalogue; final design is by the project’s approved designer to the applicable standards and the project specification.