The MECH vertical indicator post ul/fm red, model IP, UL / FM approved. It operates a buried gate valve from above ground and shows its position. This guide explains what it does and how it works, related models, technical data, the critical point in selection and installation, and common mistakes.
At a glance
- A post indicator mounts on the flange of a buried NRS gate valve and reaches the valve stem with an extension rod.
- Approvals: UL / FM.
Indicator post: what it does and how it works
A post indicator mounts on the flange of a buried NRS gate valve and reaches the valve stem with an extension rod. From above ground the valve is operated with a wrench or wheel, and its window shows “OPEN” or “SHUT”.
The vertical type stands above the buried valve; the wall type fixes to a wall to operate a valve behind it.
Related models
| Model | Product | Sizes | Pressure | Approvals |
|---|---|---|---|---|
| WP | WALL INDICATOR POST UL/FM RED | — | — | UL / FM |
| IP — this product | VERTICAL INDICATOR POST UL/FM Red | — | — | UL / FM |
Technical data
| Item | Specification |
|---|---|
| Body | Ductile iron ASTM A536 65-45-12 |
| Coating | FBE — ANSI/AWWA C550 |
| Approvals | UL / FM |
Length and target setting
Post and extension length are worked out from the valve depth. After installation the target is set to match the actual valve position.
Caution
The post must be supervised or locked open per the standard.
Installation steps
- Measure from grade to the top of the valve stem.
- Mount the post on the valve flange with the right extension rod.
- Operate the valve and set the target to the actual position.
- Lock the post or fit a supervisory switch.
Common mistakes
- Wrong length for the valve depth.
- Target not matching the actual position.
- Leaving the post unlocked and unsupervised.
Files and ordering
On this page: Product datasheet, Installation & operation manual, MECH Fire Protection Valves Catalogue (UL/FM). Add the product to your request list with size and quantity and we send a quotation, or build a submittal PDF for the consultant. Fu-Mech is the exclusive MECH agent in Saudi Arabia.
Frequently asked questions
Which valve is it used with?
NRS gate valves with an indicator-post flange.
What is the difference between vertical and wall types?
The vertical type stands above a buried valve; the wall type fixes to a wall for a valve behind it.
What approvals does it carry?
UL / FM per the product data. Check the size and listed model in the approval listings, and see how to verify UL and FM approvals.
References
- ASTM A536 — Standard Specification for Ductile Iron Castings
- AWWA C550 — Protective Interior Coatings for Valves and Hydrants
- MECH catalogue — Product datasheet
This guide is general information to help with selection. Figures come from the product data on this page and the MECH catalogue; final design is by the project’s approved designer to the applicable standards and the project specification.