Skip to content
Exclusive agent of MECH products in Saudi Arabia
Store Request a quote

TYCO TY5130 Upright Sprinkler, K11.2, 3/4″ NPT — K11-231FRB

Model TY5130

Brand
TYCO
Model
TY5130
Series
K11-231FRB
Orientation
Upright
K-factor
11.2 gpm/psi½
Thread connection
3/4" NPT
Response
Quick Response
Coverage
Standard Coverage
Temperature ratings
68 / 79 / 93 / 141 °C
Max. working pressure
175 psi (12.1 bar)
Approvals
UL · C-UL · FM · VdS · LPCB (per Table C)
Datasheet
TFP345
Request a quote for this product
Or buy from the online store

The TYCO TY5130 is the upright model of the K11-231FRB series, with a K 11.2 discharge coefficient and 3/4″ NPT thread, quick response and standard coverage, operated by a glass bulb 3 mm. It is designed for high-piled storage and high-density applications, in lieu of K 5.6 or K 8.0 standard spray sprinklers. Installed above the pipe with the deflector facing up. For where the sprinkler sits in the whole system, see the complete guide to sprinkler systems in Saudi Arabia.

In short

  • Model (SIN): TY5130 — Upright.
  • Discharge coefficient K 11.2, 3/4″ NPT connection.
  • Glass bulb 3 mm, quick response.
  • Temperature ratings in the datasheet: 68 / 79 / 93 / 141 °C.
  • Maximum working pressure: 175 psi (12.1 bar).
  • Series approvals: UL, C-UL, FM, VdS, LPCB (per Table C). The approval of each model, finish and rating is in the approvals table of datasheet TFP345.

How this sprinkler works

The glass bulb contains a fluid that expands when exposed to heat. When the rated temperature is reached, the fluid expands enough to shatter the bulb, the sprinkler opens and the deflector spreads the water over the fire area.

Installed above the pipe with the deflector facing up. Quick response means the thermal element reacts faster, so the sprinkler operates earlier than a standard-response sprinkler of the same rating.

Models in the series

Models in datasheet TFP345
SINOrientationK-factorThread
TY5130 — this modelUpright11.23/4″ NPT

Links to the other models are in the “Similar models” table below. The choice of model comes from the hydraulic calculation, hazard classification and installation method in the project design.

Application notes

  • For in-rack use it becomes an intermediate-level sprinkler with the G6/S3 guard and shield; where at risk of mechanical damage, use the G6 guard. The 79°C rating is available in chrome for Asia only.

Technical data

Technical data — TY5130 per TYCO datasheet TFP345
ItemValue
Model (SIN)TY5130
OrientationUpright
Discharge coefficientK 11.2 gpm/psi½ (161.4 L/min/bar½)
Thread3/4″ NPT
Element and responseGlass bulb 3 mm — Quick Response
CoverageStandard Coverage
Temperature ratings68 / 79 / 93 / 141 °C
Maximum working pressure175 psi (12.1 bar)
Installation torque10 – 20 lb-ft (13.4 – 26.8 N·m)
WrenchW-Type 3
ApprovalsUL, C-UL, FM, VdS, LPCB (per Table C)
DatasheetTYCO TFP345

The critical point: wrench and guard

Tighten only with the W-Type 3 wrench at 10 – 20 lb-ft; only the guard specified in the datasheet may be used.

Installation steps

  1. Inspect before installing: never install a sprinkler whose bulb is cracked or has lost liquid.
  2. Install the sprinkler in its correct orientation (Upright) as shown in the datasheet — never reversed.
  3. Apply pipe-thread sealant to the threads, then hand-tighten the sprinkler.
  4. Finish with the specified wrench (W-Type 3) within 10 – 20 lb-ft (13.4 – 26.8 N·m). Higher torque can distort the inlet and cause leakage.

Common mistakes

  • Installing a sprinkler that was dropped, struck or slipped by the wrench. The datasheet requires any such sprinkler to be replaced.
  • Painting or coating sprinklers on site. Sprinklers must not be altered after leaving the factory; altered sprinklers are replaced.
  • Hanging objects from sprinklers, or cleaning them with anything other than a gentle feather duster.

Maintenance

Sprinklers that leak or show visible corrosion must be replaced, as must sprinklers exposed to corrosive products of combustion that cannot be fully cleaned. The owner is responsible for inspection, testing and maintenance to NFPA 25 and the authority having jurisdiction, preferably by a qualified inspection service. Before closing a main control valve for maintenance, obtain permission from the proper authorities and notify everyone affected.

Files and ordering

TYCO datasheet TFP345 and the available approval certificates are in the files section of this page. When ordering, state the model TY5130, temperature rating and finish. The datasheet lists the part numbers (P/N) for each combination.

How to order

Use the “Build your order” section on this page: add every model and quantity, then send the whole order by email or WhatsApp. It reaches us as a tidy PDF request sheet and we contact you with the quotation.

FAQ

What does TY5130 mean?

It is TYCO’s Sprinkler Identification Number (SIN). It identifies the exact model — orientation, K-factor and thread. The sprinkler is ordered by this number together with temperature rating and finish.

How do I choose the temperature rating?

From the highest expected ceiling temperature and the rating classes in the project’s governing standard, within the ratings available for this model in the datasheet.

Do all models in the series carry the same approvals?

Not always. The approvals table in datasheet TFP345 gives each model’s approvals by rating and finish, so check it when the project requires a specific approval.

What is the benefit of quick response?

The thermal element reacts faster, so the sprinkler operates earlier and limits heat and smoke spread; standards require it in some occupancies such as light hazard.

References

  • TYCO TFP345 — Series datasheet (attached)
  • NFPA 13 — Standard for the Installation of Sprinkler Systems
  • NFPA 25 — Inspection, Testing and Maintenance of Water-Based Fire Protection Systems
  • TYCO TFP700 — Installer warning for handling and installing sprinklers

This page is general information to help with selection and ordering, taken from the attached TYCO datasheet. Final design is set by the project’s approved designer; the project specification, the consultant’s drawings and the latest datasheet revision govern.

Similar models

Same type — compare K-factor, response and approvals to pick the right one.

ProductModelKResponseApprovals
TYCO TY1131 Upright Sprinkler, K2.8, 1/2″ NPT — TY-FRB2.8Quick ResponseUL · C-UL · FM · LPCB · VdS (per Tables A–D)
TYCO TY1231 Pendent / Recessed Pendent Sprinkler, K2.8, 1/2″ NPT — TY-FRB2.8Quick ResponseUL · C-UL · FM · LPCB · VdS (per Tables A–D)
TYCO TY2131 Upright Sprinkler, K4.2, 1/2″ NPT — TY-FRB4.2Quick ResponseUL · C-UL · FM · LPCB · VdS (per Tables A–D)
TYCO TY2231 Pendent / Recessed Pendent Sprinkler, K4.2, 1/2″ NPT — TY-FRB4.2Quick ResponseUL · C-UL · FM · LPCB · VdS (per Tables A–D)
TYCO TY3111 Upright Sprinkler, K5.6, 1/2″ NPT — TY-L5.6Standard ResponseUL · C-UL · FM · EAC
TYCO TY313 Upright Sprinkler, K5.6, 1/2″ NPT — TY-FRB5.6Quick ResponseUL · C-UL · FM · LPCB · VdS (per Table A)
TYCO TY3131 Upright Sprinkler, K5.6, 1/2″ NPT — TY-FRB5.6Quick ResponseUL · C-UL · FM · LPCB · VdS (per Tables A–D)
TYCO TY315 Upright Sprinkler, K5.6, 1/2″ NPT — TY-B5.6Standard ResponseUL · C-UL · FM · LPCB · VdS (per Table A)
TYCO TY3151 Upright Sprinkler, K5.6, 1/2″ NPT — TY-B5.6Standard ResponseUL · C-UL · FM; LPCB / VdS for specific models
TYCO TY3153 Upright Sprinkler, K5.6, 1/2″ NPT — TY-B Intermediate Level5.6Standard ResponseUL · C-UL · FM
TYCO TY3211 Pendent / Recessed Pendent Sprinkler, K5.6, 1/2″ NPT — TY-L5.6Standard ResponseUL · C-UL · FM · EAC
TYCO TY323 Pendent / Recessed Pendent Sprinkler, K5.6, 1/2″ NPT — TY-FRB5.6Quick ResponseUL · C-UL · FM · LPCB · VdS (per Table A)