Skip to content
Exclusive agent of MECH products in Saudi Arabia
Store Request a quote

TYCO TY3521 Concealed Horizontal Sidewall Sprinkler, K5.6, 1/2″ NPT — RFII HSW

Model TY3521

Brand
TYCO
Model
TY3521
Series
RFII HSW
Orientation
Concealed Horizontal Sidewall
K-factor
5.6 gpm/psi½
Thread connection
1/2" NPT
Response
Quick Response
Coverage
Standard Coverage
Temperature ratings
71°C sprinkler with 59°C plate, or 100°C sprinkler with 74°C plate
Max. working pressure
175 psi (12.1 bar); 250 psi under UL and C-UL
Approvals
UL · C-UL · FM (standard response only)
Datasheet
TFP185
Request a quote for this product
Or buy from the online store

The TYCO TY3521 is the concealed horizontal sidewall model of the RFII HSW series, with a K 5.6 discharge coefficient and 1/2″ NPT thread, quick response and standard coverage, operated by a fusible link. It is designed for architecturally sensitive areas such as hotel rooms, dormitories, reception areas, offices and hospitals. Installed within the wall with only a flat cover plate visible. For where the sprinkler sits in the whole system, see the complete guide to sprinkler systems in Saudi Arabia.

In short

  • Model (SIN): TY3521 — Concealed Horizontal Sidewall.
  • Discharge coefficient K 5.6, 1/2″ NPT connection.
  • Fusible link, quick response.
  • Temperature ratings in the datasheet: 71°C sprinkler with 59°C plate, or 100°C sprinkler with 74°C plate.
  • Maximum working pressure: 175 psi (12.1 bar); 250 psi under UL and C-UL.
  • Series approvals: UL, C-UL, FM (standard response only). The approval of each model, finish and rating is in the approvals table of datasheet TFP185.

How this sprinkler works

The fusible link is made of two halves joined by a thin layer of solder. When the rated temperature is reached the solder melts, the halves separate and the sprinkler opens to flow water.

In a concealed sprinkler the flat cover plate is soldered to the retainer at three points with a solder rated lower than the sprinkler. Fire heat first drops the cover plate, the deflector drops on its guide pins to the operating position, then the sprinkler operates at its own rating.

Installed within the wall with only a flat cover plate visible. Quick response means the thermal element reacts faster, so the sprinkler operates earlier than a standard-response sprinkler of the same rating.

Models in the series

Models in datasheet TFP185
SINOrientationK-factorThread
TY3521 — this modelConcealed Horizontal Sidewall5.61/2″ NPT

Links to the other models are in the “Similar models” table below. The choice of model comes from the hydraulic calculation, hazard classification and installation method in the project design.

Application notes

  • FM approval is as standard response only, as FM does not approve concealed sprinklers as quick response. The pipe guide bracket is required for CPVC installations only.

Technical data

Technical data — TY3521 per TYCO datasheet TFP185
ItemValue
Model (SIN)TY3521
OrientationConcealed Horizontal Sidewall
Discharge coefficientK 5.6 gpm/psi½ (80.6 L/min/bar½)
Thread1/2″ NPT
Element and responseFusible link — Quick Response
CoverageStandard Coverage
Temperature ratings71°C sprinkler with 59°C plate, or 100°C sprinkler with 74°C plate
Maximum working pressure175 psi (12.1 bar); 250 psi under UL and C-UL
Installation torque7 – 14 lb-ft (9.5 – 19.0 N·m)
WrenchW-Type 37
ApprovalsUL, C-UL, FM (standard response only)
DatasheetTYCO TFP185

The critical point: centreline and cover

Install with its centreline perpendicular to the back wall and parallel to the ceiling, only with factory-finished LFII/RFIII cover plates, never repainted.

Installation steps

  1. Install the sprinkler in its correct orientation (Concealed Horizontal Sidewall) as shown in the datasheet — never reversed.
  2. Apply pipe-thread sealant to the threads, then hand-tighten the sprinkler.
  3. Finish with the specified wrench (W-Type 37) within 7 – 14 lb-ft (9.5 – 19.0 N·m). Higher torque can distort the inlet and cause leakage.
  4. After the ceiling or wall is finished and the system pressure tested, fit the specified cover plate until its flange touches the surface — never painted.

Common mistakes

  • Repainting the cover plate or replacing it with an unspecified one. The sprinkler is listed only with its factory-finished cover plates.
  • Installing a sprinkler that was dropped, struck or slipped by the wrench. The datasheet requires any such sprinkler to be replaced.
  • Painting or coating sprinklers on site. Sprinklers must not be altered after leaving the factory; altered sprinklers are replaced.
  • Hanging objects from sprinklers, or cleaning them with anything other than a gentle feather duster.

Maintenance

Sprinklers that leak or show visible corrosion must be replaced, as must sprinklers exposed to corrosive products of combustion that cannot be fully cleaned. The owner is responsible for inspection, testing and maintenance to NFPA 25 and the authority having jurisdiction, preferably by a qualified inspection service. Before closing a main control valve for maintenance, obtain permission from the proper authorities and notify everyone affected.

Files and ordering

TYCO datasheet TFP185 and the available approval certificates are in the files section of this page. When ordering, state the model TY3521, temperature rating and finish, cover plate. The datasheet lists the part numbers (P/N) for each combination.

How to order

Use the “Build your order” section on this page: add every model and quantity, then send the whole order by email or WhatsApp. It reaches us as a tidy PDF request sheet and we contact you with the quotation.

FAQ

What does TY3521 mean?

It is TYCO’s Sprinkler Identification Number (SIN). It identifies the exact model — orientation, K-factor and thread. The sprinkler is ordered by this number together with temperature rating and finish.

How do I choose the temperature rating?

From the highest expected ceiling temperature and the rating classes in the project’s governing standard, within the ratings available for this model in the datasheet.

Do all models in the series carry the same approvals?

Not always. The approvals table in datasheet TFP185 gives each model’s approvals by rating and finish, so check it when the project requires a specific approval.

What is the benefit of quick response?

The thermal element reacts faster, so the sprinkler operates earlier and limits heat and smoke spread; standards require it in some occupancies such as light hazard.

When does the cover plate drop?

The plate is soldered with a lower-rated solder than the sprinkler, so it drops first in a fire; the deflector then drops and the sprinkler operates at its own rating.

References

  • TYCO TFP185 — Series datasheet (attached)
  • NFPA 13 — Standard for the Installation of Sprinkler Systems
  • NFPA 25 — Inspection, Testing and Maintenance of Water-Based Fire Protection Systems
  • TYCO TFP700 — Installer warning for handling and installing sprinklers

This page is general information to help with selection and ordering, taken from the attached TYCO datasheet. Final design is set by the project’s approved designer; the project specification, the consultant’s drawings and the latest datasheet revision govern.

Similar models

Same type — compare K-factor, response and approvals to pick the right one.