Skip to content
Exclusive agent of MECH products in Saudi Arabia
Store Request a quote

TYCO TY3281 Institutional Pendent Sprinkler, K5.6, 1/2″ NPT — RAVEN Institutional

Model TY3281

Brand
TYCO
Model
TY3281
Series
RAVEN Institutional
Orientation
Institutional Pendent
K-factor
5.6 gpm/psi½
Thread connection
1/2" NPT
Response
Quick Response
Coverage
Institutional sprinkler
Temperature ratings
74°C
Max. working pressure
175 psi (12.1 bar)
Approvals
UL · C-UL
Datasheet
TFP651
Request a quote for this product
Or buy from the online store

The TYCO TY3281 is the institutional pendent model of the RAVEN Institutional series, with a K 5.6 discharge coefficient and 1/2″ NPT thread, quick response and institutional sprinkler, operated by a fusible link. It is designed for correctional, detention and mental health facilities, and other commercial buildings. Installed pendent, with a tamper-resistant design. For where the sprinkler sits in the whole system, see the complete guide to sprinkler systems in Saudi Arabia.

In short

  • Model (SIN): TY3281 — Institutional Pendent.
  • Discharge coefficient K 5.6, 1/2″ NPT connection.
  • Fusible link, quick response.
  • Temperature ratings in the datasheet: 74°C.
  • Maximum working pressure: 175 psi (12.1 bar).
  • Series approvals: UL, C-UL. The approval of each model, finish and rating is in the approvals table of datasheet TFP651.
  • Standard coverage (light and ordinary hazard) — black ID dot.

How this sprinkler works

The fusible link is made of two halves joined by a thin layer of solder. When the rated temperature is reached the solder melts, the halves separate and the sprinkler opens to flow water.

Installed pendent, with a tamper-resistant design. Quick response means the thermal element reacts faster, so the sprinkler operates earlier than a standard-response sprinkler of the same rating.

Models in the series

Models in datasheet TFP651
SINOrientationK-factorThread
TY3281 — this modelInstitutional Pendent5.61/2″ NPT
TY3282Institutional Pendent5.61/2″ NPT
TY3381Institutional Horizontal Sidewall5.61/2″ NPT
TY3382Institutional Horizontal Sidewall5.61/2″ NPT

Links to the other models are in the “Similar models” table below. The choice of model comes from the hydraulic calculation, hazard classification and installation method in the project design.

Application notes

  • A tamper-resistant design that helps prevent false activation and minimises parts and openings that objects could be tied to. The sprinkler is designed to operate if the inner link is removed manually, so a tampered sprinkler is never left inoperable.

Technical data

Technical data — TY3281 per TYCO datasheet TFP651
ItemValue
Model (SIN)TY3281
OrientationInstitutional Pendent
Discharge coefficientK 5.6 gpm/psi½ (80.6 L/min/bar½)
Thread1/2″ NPT
Element and responseFusible link — Quick Response
CoverageInstitutional sprinkler
Temperature ratings74°C
Maximum working pressure175 psi (12.1 bar)
Installation torque7 – 14 lb-ft (9.5 – 19.0 N·m)
WrenchW-Type 25
EscutcheonOnly the escutcheons shown in the datasheet
ApprovalsUL, C-UL
DatasheetTYCO TFP651

The critical point: the specified escutcheon

Use only the escutcheons shown in the datasheet, tightening with the W-Type 25 wrench at 7 – 14 lb-ft so the escutcheon is held fast to the ceiling or wall.

Installation steps

  1. Install the sprinkler in its correct orientation (Institutional Pendent) as shown in the datasheet — never reversed.
  2. Apply pipe-thread sealant to the threads, then hand-tighten the sprinkler.
  3. Finish with the specified wrench (W-Type 25) within 7 – 14 lb-ft (9.5 – 19.0 N·m). Higher torque can distort the inlet and cause leakage.
  4. With an escutcheon, use only the specified one (Only the escutcheons shown in the datasheet) and never compensate for adjustment by changing the torque.

Common mistakes

  • Installing a sprinkler that was dropped, struck or slipped by the wrench. The datasheet requires any such sprinkler to be replaced.
  • Painting or coating sprinklers on site. Sprinklers must not be altered after leaving the factory; altered sprinklers are replaced.
  • Hanging objects from sprinklers, or cleaning them with anything other than a gentle feather duster.

Maintenance

Sprinklers that leak or show visible corrosion must be replaced, as must sprinklers exposed to corrosive products of combustion that cannot be fully cleaned. The owner is responsible for inspection, testing and maintenance to NFPA 25 and the authority having jurisdiction, preferably by a qualified inspection service. Before closing a main control valve for maintenance, obtain permission from the proper authorities and notify everyone affected.

Files and ordering

TYCO datasheet TFP651 and the available approval certificates are in the files section of this page. When ordering, state the model TY3281, temperature rating and finish, escutcheon. The datasheet lists the part numbers (P/N) for each combination.

How to order

Use the “Build your order” section on this page: add every model and quantity, then send the whole order by email or WhatsApp. It reaches us as a tidy PDF request sheet and we contact you with the quotation.

FAQ

What does TY3281 mean?

It is TYCO’s Sprinkler Identification Number (SIN). It identifies the exact model — orientation, K-factor and thread. The sprinkler is ordered by this number together with temperature rating and finish.

How do I choose the temperature rating?

From the highest expected ceiling temperature and the rating classes in the project’s governing standard, within the ratings available for this model in the datasheet.

Do all models in the series carry the same approvals?

Not always. The approvals table in datasheet TFP651 gives each model’s approvals by rating and finish, so check it when the project requires a specific approval.

What is the benefit of quick response?

The thermal element reacts faster, so the sprinkler operates earlier and limits heat and smoke spread; standards require it in some occupancies such as light hazard.

References

  • TYCO TFP651 — Series datasheet (attached)
  • NFPA 13 — Standard for the Installation of Sprinkler Systems
  • NFPA 25 — Inspection, Testing and Maintenance of Water-Based Fire Protection Systems
  • TYCO TFP700 — Installer warning for handling and installing sprinklers

This page is general information to help with selection and ordering, taken from the attached TYCO datasheet. Final design is set by the project’s approved designer; the project specification, the consultant’s drawings and the latest datasheet revision govern.

Similar models

Same type — compare K-factor, response and approvals to pick the right one.