Skip to content
Exclusive agent of MECH products in Saudi Arabia
Store Request a quote

TYCO TY3532 Concealed Pendent Sprinkler, K5.6, 1/2″ NPT — RFII ECLH

Model TY3532

Brand
TYCO
Model
TY3532
Series
RFII ECLH
Orientation
Concealed Pendent
K-factor
5.6 gpm/psi½
Thread connection
1/2" NPT
Response
Quick Response
Coverage
Extended Coverage
Temperature ratings
68°C sprinkler with 59°C plate, or 93°C sprinkler with 74°C plate
Max. working pressure
175 psi (12.1 bar)
Approvals
UL · C-UL · NYC
Datasheet
TFP260
Request a quote for this product
Or buy from the online store

The TYCO TY3532 is the concealed pendent model of the RFII ECLH series, with a K 5.6 discharge coefficient and 1/2″ NPT thread, quick response and extended coverage, operated by a glass bulb 3 mm. It is designed for architecturally sensitive light hazard areas, with extended coverage. Installed in a finished ceiling with only a flat cover plate visible. For where the sprinkler sits in the whole system, see the complete guide to sprinkler systems in Saudi Arabia.

In short

  • Model (SIN): TY3532 — Concealed Pendent.
  • Discharge coefficient K 5.6, 1/2″ NPT connection.
  • Glass bulb 3 mm, quick response.
  • Temperature ratings in the datasheet: 68°C sprinkler with 59°C plate, or 93°C sprinkler with 74°C plate.
  • Maximum working pressure: 175 psi (12.1 bar).
  • Series approvals: UL, C-UL, NYC. The approval of each model, finish and rating is in the approvals table of datasheet TFP260.

How this sprinkler works

The glass bulb contains a fluid that expands when exposed to heat. When the rated temperature is reached, the fluid expands enough to shatter the bulb, the sprinkler opens and the deflector spreads the water over the fire area.

In a concealed sprinkler the flat cover plate is soldered to the retainer at three points with a solder rated lower than the sprinkler. Fire heat first drops the cover plate, the deflector drops on its guide pins to the operating position, then the sprinkler operates at its own rating.

Installed in a finished ceiling with only a flat cover plate visible. Quick response means the thermal element reacts faster, so the sprinkler operates earlier than a standard-response sprinkler of the same rating.

Models in the series

Models in datasheet TFP260
SINOrientationK-factorThread
TY3532 — this modelConcealed Pendent5.61/2″ NPT

Links to the other models are in the “Similar models” table below. The choice of model comes from the hydraulic calculation, hazard classification and installation method in the project design.

Application notes

  • A concealed extended coverage light hazard (ECLH) sprinkler with fast-response sensitivity, for systems designed to NFPA 13.

Technical data

Technical data — TY3532 per TYCO datasheet TFP260
ItemValue
Model (SIN)TY3532
OrientationConcealed Pendent
Discharge coefficientK 5.6 gpm/psi½ (80.6 L/min/bar½)
Thread1/2″ NPT
Element and responseGlass bulb 3 mm — Quick Response
CoverageExtended Coverage
Temperature ratings68°C sprinkler with 59°C plate, or 93°C sprinkler with 74°C plate
Maximum working pressure175 psi (12.1 bar)
Installation torque7 – 14 lb-ft (9.5 – 19.0 N·m)
WrenchRFII Sprinkler Wrench
ApprovalsUL, C-UL, NYC
DatasheetTYCO TFP260

The critical point: the cover plate is part of the listing

The sprinkler is listed only with its specified cover plates with factory-applied finish. Do not repaint the plate or substitute another.

Installation steps

  1. Inspect before installing: never install a sprinkler whose bulb is cracked or has lost liquid.
  2. Install the sprinkler in its correct orientation (Concealed Pendent) as shown in the datasheet — never reversed.
  3. Apply pipe-thread sealant to the threads, then hand-tighten the sprinkler.
  4. Finish with the specified wrench (RFII Sprinkler Wrench) within 7 – 14 lb-ft (9.5 – 19.0 N·m). Higher torque can distort the inlet and cause leakage.
  5. After the ceiling or wall is finished and the system pressure tested, fit the specified cover plate until its flange touches the surface — never painted.

Common mistakes

  • Repainting the cover plate or replacing it with an unspecified one. The sprinkler is listed only with its factory-finished cover plates.
  • Installing a sprinkler that was dropped, struck or slipped by the wrench. The datasheet requires any such sprinkler to be replaced.
  • Painting or coating sprinklers on site. Sprinklers must not be altered after leaving the factory; altered sprinklers are replaced.
  • Hanging objects from sprinklers, or cleaning them with anything other than a gentle feather duster.

Maintenance

Sprinklers that leak or show visible corrosion must be replaced, as must sprinklers exposed to corrosive products of combustion that cannot be fully cleaned. The owner is responsible for inspection, testing and maintenance to NFPA 25 and the authority having jurisdiction, preferably by a qualified inspection service. Before closing a main control valve for maintenance, obtain permission from the proper authorities and notify everyone affected.

Files and ordering

TYCO datasheet TFP260 and the available approval certificates are in the files section of this page. When ordering, state the model TY3532, temperature rating and finish, cover plate. The datasheet lists the part numbers (P/N) for each combination.

How to order

Use the “Build your order” section on this page: add every model and quantity, then send the whole order by email or WhatsApp. It reaches us as a tidy PDF request sheet and we contact you with the quotation.

FAQ

What does TY3532 mean?

It is TYCO’s Sprinkler Identification Number (SIN). It identifies the exact model — orientation, K-factor and thread. The sprinkler is ordered by this number together with temperature rating and finish.

How do I choose the temperature rating?

From the highest expected ceiling temperature and the rating classes in the project’s governing standard, within the ratings available for this model in the datasheet.

Do all models in the series carry the same approvals?

Not always. The approvals table in datasheet TFP260 gives each model’s approvals by rating and finish, so check it when the project requires a specific approval.

What is the benefit of quick response?

The thermal element reacts faster, so the sprinkler operates earlier and limits heat and smoke spread; standards require it in some occupancies such as light hazard.

When does the cover plate drop?

The plate is soldered with a lower-rated solder than the sprinkler, so it drops first in a fire; the deflector then drops and the sprinkler operates at its own rating.

References

  • TYCO TFP260 — Series datasheet (attached)
  • NFPA 13 — Standard for the Installation of Sprinkler Systems
  • NFPA 25 — Inspection, Testing and Maintenance of Water-Based Fire Protection Systems
  • TYCO TFP700 — Installer warning for handling and installing sprinklers

This page is general information to help with selection and ordering, taken from the attached TYCO datasheet. Final design is set by the project’s approved designer; the project specification, the consultant’s drawings and the latest datasheet revision govern.

Similar models

Same type — compare K-factor, response and approvals to pick the right one.

ProductModelKResponseApprovals
TYCO TY3521 Concealed Horizontal Sidewall Sprinkler, K5.6, 1/2″ NPT — RFII HSW5.6Quick ResponseUL · C-UL · FM (standard response only)
TYCO TY3531 Concealed Pendent Sprinkler, K5.6, 1/2″ NPT — RFII Royal Flush II5.6Quick ResponseUL · C-UL · FM · LPCB · VdS · NYC (per datasheet)
TYCO TY3551 Concealed Pendent Sprinkler, K5.6, 1/2″ NPT — RFII Royal Flush II5.6Standard ResponseUL · C-UL · FM · LPCB · VdS · NYC (per datasheet)
TYCO TY4332 Concealed Horizontal Sidewall Sprinkler, K8.0, 3/4″ NPT — CHEC8.0Quick ResponseUL · C-UL · NYC
TYCO TY4522 Concealed Horizontal Sidewall Sprinkler, K8.0, 3/4″ NPT — RFIII ECLH8.0Quick ResponseUL · C-UL · EAC
TYCO TY5521 Concealed Pendent Sprinkler, K11.2, 3/4″ NPT — ILLUSION11.2Quick ResponseUL · C-UL