The MECH grooved end cap (thd), model 300TX, in ductile iron, sizes 2″ × 1″ – 8″ × 1″ (DN50×25 – DN200×25), working pressure up to 500 PSI, UL / FM / VdS approved depending on size. This guide explains what it does and how it works, compares it with related models, and covers technical data, the critical point in selection and installation, and common mistakes. For more, read the technical library guide.
At a glance
- A grooved end cap closes the end of a grooved pipe and joins with a grooved coupling like any other fitting, so it is easy to remove later to extend the line or for maintenance.
- Sizes 2″ × 1″ – 8″ × 1″ (DN50×25 – DN200×25) — working pressure up to 500 PSI.
- Approvals: UL / FM / VdS (vary by size).
- Material Ductile iron ASTM A536 Gr. 65-45-12.
- Designed to ASTM F1548, AWWA C606, ISO 6182-12.
What is a grooved end cap and how does it work?
A grooved end cap closes the end of a grooved pipe and joins with a grooved coupling like any other fitting, so it is easy to remove later to extend the line or for maintenance.
Some models have a threaded tapping (central, or eccentric near the edge) to connect a drain, vent or gauge without an extra fitting.
About model 300TX: A cap with a female-threaded tapping.
Models in the same family
| Model | Item | Sizes | Max pressure | Approvals |
|---|---|---|---|---|
| 300PX | MECH GROOVED CAP EXCEN HOLE | 2-1/2″ × 1″ – 12″ × 1-1/2″ | 500 PSI | UL / FM / VdS |
| 300TX — this product | MECH GROOVED END CAP (THD) | 2″ × 1″ – 8″ × 1″ | 500 PSI | UL / FM / VdS |
| 300 | MECH GROOVED END CAP | 1″ – 24″ | 500 PSI | UL / FM / VdS / LPCB |
Technical data
| Item | Specification |
|---|---|
| Design standard | ASTM F1548, AWWA C606, ISO 6182-12 |
| Material | Ductile iron ASTM A536 Gr. 65-45-12 |
| Coating | Electrophoretic (std.) — epoxy / hot-dip galvanized optional |
| Sizes | 2″ × 1″ – 8″ × 1″ (DN50×25 – DN200×25) |
| Approvals | Sizes | Working pressure |
|---|---|---|
| VdS | 2″ × 1″ – 2-1/2″ × 2″ | 500 PSI |
| Not stated in the table | 2-1/2″ × 1″ – 6″ × 1″ | 500 PSI |
| UL | 2-1/2″ × 1-1/2″ – 6″ × 1-1/2″ | 500 PSI |
| UL / FM | 3″ × 1/2″ – 8″ × 1″ | 500 PSI |
| UL / VdS | 3″ × 2″ | 500 PSI |
Some sizes come in two pipe outside diameters (for example 73.0 and 76.1 mm for 2-1/2″) depending on the pipe standard; select by the actual outside diameter of your project pipe.
Full dimensions for every size (bolts and more) are in the size table at the top of the page.
Pressure thrust on the cap
A cap at the end of a line takes the full thrust from water pressure, carried by the groove and coupling, so the coupling must suit the pressure and be fitted correctly.
Caution
Never remove an end cap or its coupling while the line is under pressure; release the pressure and drain first.
Installation steps
- Check that the pipe ends are grooved to the right dimensions to AWWA C606 (roll or cut groove) and are free of burrs, rust and dirt.
- Inspect the gasket and lubricate its outside and lips with the lubricant recommended in the MECH catalogue; never use petroleum-based products with an EPDM gasket.
- Fit the gasket over one pipe end, bring the other end or the fitting into place, and slide the gasket so it is centred between the two grooves.
- Place both housing halves over the gasket so their keys engage the grooves on both sides.
- Hand-tighten the nuts first, making sure each oval-neck bolt sits in its hole, then tighten alternately and evenly to the torque in the MECH installation manual — never exceed it.
The fitting joins with grooved couplings; how the joint is finished (even pad gap or pads meeting) follows the coupling type in the MECH manual.
Full details and bolt torques are in the MECH installation manual among the files on this page.
Common mistakes
- Letting the gasket lip overhang the pipe end or protrude into a groove, so the gasket is not centred on the joint.
- Exceeding the specified bolt torque, which can damage the bolt or the joint.
- Grooves that do not meet AWWA C606 dimensions, or pipe ends that are not square.
- Tightening the nuts on one side only, so the housing tilts and the key does not seat in the groove.
- Using petroleum-based lubricant that damages the EPDM gasket.
Files and ordering
On this page: Product page (catalogue), MECH Grooved Fittings & Couplings Catalogue, Installation & operation manual, Material Safety Data Sheet (MSDS). Add the product to your request list with size and quantity and we send a quotation, or build a submittal PDF for the consultant. Fu-Mech is the exclusive MECH agent in Saudi Arabia.
Frequently asked questions
When should I choose a cap with a tapping?
When you need a drain, vent or gauge point at the end of the line. An eccentric tapping sits near the edge, useful for draining or venting from the bottom or top of the pipe. See the guide grooved end caps.
What is the maximum working pressure of model 300TX?
Up to 500 PSI. The pressure for each size is in the size table.
Is model 300TX UL / FM approved?
Approvals for this model: UL / FM / VdS, varying by size as shown in the “Approvals and pressure by size” table above. See also how to verify UL and FM approvals.
What is the gasket material, and does it suit all fluids?
Gasket type and suitable services are given in the MECH catalogue.
Does it suit roll-grooved and cut-grooved pipe?
Grooves are to AWWA C606, rolled or cut; what matters is correct groove dimensions. The difference is explained in the guide roll grooving vs cut grooving.
References
- ASTM F1548 — Standard Specification for Performance of Fittings for Use with Gasketed Mechanical Couplings Used in Piping Applications
- AWWA C606 — Grooved and Shouldered Joints
- ISO 6182-12 — Fire protection — Automatic sprinkler systems — Requirements and test methods for grooved-end components for steel pipe systems
- ASTM A536 — Standard Specification for Ductile Iron Castings
- UL 213 — Rubber Gasketed Fittings for Fire-Protection Service
- FM 1920 — Approval Standard for Pipe Couplings and Fittings for Fire Protection Systems
- MECH catalogue — Grooved Fittings & Couplings — and installation manual
This guide is general information to help with selection. Figures come from the product data on this page and the MECH catalogue; final design is by the project’s approved designer to NFPA 13 and the project specification.