Skip to content
Exclusive agent of MECH products in Saudi Arabia
Store Request a quote

TYCO TY1131 Upright Sprinkler, K2.8, 1/2″ NPT — TY-FRB

Model TY1131

Brand
TYCO
Model
TY1131
Series
TY-FRB
Orientation
Upright
K-factor
2.8 gpm/psi½
Thread connection
1/2" NPT
Response
Quick Response
Coverage
Standard Coverage
Temperature ratings
57 / 68 / 79 / 93 / 141 °C
Max. working pressure
Per Table E of the datasheet (175 psi; 250 psi under UL for some models)
Approvals
UL · C-UL · FM · LPCB · VdS (per Tables A–D)
Datasheet
TFP171
Request a quote for this product
Or buy from the online store

The TYCO TY1131 is the upright model of the TY-FRB series, with a K 2.8 discharge coefficient and 1/2″ NPT thread, quick response and standard coverage, operated by a glass bulb 3 mm. It is designed for light and ordinary hazard commercial occupancies such as banks, hotels and shopping malls. Installed above the pipe with the deflector facing up. For where the sprinkler sits in the whole system, see the complete guide to sprinkler systems in Saudi Arabia.

In short

  • Model (SIN): TY1131 — Upright.
  • Discharge coefficient K 2.8, 1/2″ NPT connection.
  • Glass bulb 3 mm, quick response.
  • Temperature ratings in the datasheet: 57 / 68 / 79 / 93 / 141 °C.
  • Maximum working pressure: Per Table E of the datasheet (175 psi; 250 psi under UL for some models).
  • Series approvals: UL, C-UL, FM, LPCB, VdS (per Tables A–D). The approval of each model, finish and rating is in the approvals table of datasheet TFP171.

How this sprinkler works

The glass bulb contains a fluid that expands when exposed to heat. When the rated temperature is reached, the fluid expands enough to shatter the bulb, the sprinkler opens and the deflector spreads the water over the fire area.

Installed above the pipe with the deflector facing up. Quick response means the thermal element reacts faster, so the sprinkler operates earlier than a standard-response sprinkler of the same rating.

Models in the series

Models in datasheet TFP171
SINOrientationK-factorThread
TY1131 — this modelUpright2.81/2″ NPT
TY1231Pendent / Recessed Pendent2.81/2″ NPT
TY2131Upright4.21/2″ NPT
TY2231Pendent / Recessed Pendent4.21/2″ NPT
TY3131Upright5.61/2″ NPT
TY3231Pendent / Recessed Pendent5.61/2″ NPT
TY4131Upright8.03/4″ NPT
TY4231Pendent / Recessed Pendent8.03/4″ NPT
TY4831Upright8.01/2″ NPT
TY4931Pendent8.01/2″ NPT

Links to the other models are in the “Similar models” table below. The choice of model comes from the hydraulic calculation, hazard classification and installation method in the project design.

Application notes

  • Quick response with a 3 mm bulb, so it operates earlier than standard-response sprinklers of the same temperature rating.
  • Corrosion-resistant finishes are available per the datasheet for corrosive atmospheres; the datasheet notes that corrosion tests do not represent every possible atmosphere, so suitability for the actual environment should be checked.

Technical data

Technical data — TY1131 per TYCO datasheet TFP171
ItemValue
Model (SIN)TY1131
OrientationUpright
Discharge coefficientK 2.8 gpm/psi½ (40.3 L/min/bar½)
Thread1/2″ NPT
Element and responseGlass bulb 3 mm — Quick Response
CoverageStandard Coverage
Temperature ratings57 / 68 / 79 / 93 / 141 °C
Maximum working pressurePer Table E of the datasheet (175 psi; 250 psi under UL for some models)
Installation torque7 – 14 lb-ft (9.5 – 19.0 N·m)
WrenchW-Type 6 (W-Type 7 for recessed)
EscutcheonRecessed pendent: Style 10 / 20 (1/2″) or Style 30 / 40 (3/4″)
ApprovalsUL, C-UL, FM, LPCB, VdS (per Tables A–D)
DatasheetTYCO TFP171

The critical point: wrench and torque

Tighten only with the specified wrench on the wrench flats, within the torque for its thread. Higher torque can distort the inlet and cause leakage or impairment.

Do not compensate for too little escutcheon adjustment by under- or over-tightening; readjust the sprinkler fitting.

Installation steps

  1. Inspect before installing: never install a sprinkler whose bulb is cracked or has lost liquid.
  2. Install the sprinkler in its correct orientation (Upright) as shown in the datasheet — never reversed.
  3. Apply pipe-thread sealant to the threads, then hand-tighten the sprinkler.
  4. Finish with the specified wrench (W-Type 6 (W-Type 7 for recessed)) within 7 – 14 lb-ft (9.5 – 19.0 N·m). Higher torque can distort the inlet and cause leakage.

Common mistakes

  • Installing a sprinkler that was dropped, struck or slipped by the wrench. The datasheet requires any such sprinkler to be replaced.
  • Painting or coating sprinklers on site. Sprinklers must not be altered after leaving the factory; altered sprinklers are replaced.
  • Hanging objects from sprinklers, or cleaning them with anything other than a gentle feather duster.

Maintenance

Sprinklers that leak or show visible corrosion must be replaced, as must sprinklers exposed to corrosive products of combustion that cannot be fully cleaned. The owner is responsible for inspection, testing and maintenance to NFPA 25 and the authority having jurisdiction, preferably by a qualified inspection service. Before closing a main control valve for maintenance, obtain permission from the proper authorities and notify everyone affected.

Files and ordering

TYCO datasheet TFP171 and the available approval certificates are in the files section of this page. When ordering, state the model TY1131, temperature rating and finish, escutcheon. The datasheet lists the part numbers (P/N) for each combination.

How to order

Use the “Build your order” section on this page: add every model and quantity, then send the whole order by email or WhatsApp. It reaches us as a tidy PDF request sheet and we contact you with the quotation.

FAQ

What does TY1131 mean?

It is TYCO’s Sprinkler Identification Number (SIN). It identifies the exact model — orientation, K-factor and thread. The sprinkler is ordered by this number together with temperature rating and finish.

How do I choose the temperature rating?

From the highest expected ceiling temperature and the rating classes in the project’s governing standard, within the ratings available for this model in the datasheet.

Do all models in the series carry the same approvals?

Not always. The approvals table in datasheet TFP171 gives each model’s approvals by rating and finish, so check it when the project requires a specific approval.

What is the benefit of quick response?

The thermal element reacts faster, so the sprinkler operates earlier and limits heat and smoke spread; standards require it in some occupancies such as light hazard.

References

  • TYCO TFP171 — Series datasheet (attached)
  • NFPA 13 — Standard for the Installation of Sprinkler Systems
  • NFPA 25 — Inspection, Testing and Maintenance of Water-Based Fire Protection Systems
  • TYCO TFP700 — Installer warning for handling and installing sprinklers

This page is general information to help with selection and ordering, taken from the attached TYCO datasheet. Final design is set by the project’s approved designer; the project specification, the consultant’s drawings and the latest datasheet revision govern.

Similar models

Same type — compare K-factor, response and approvals to pick the right one.

ProductModelKResponseApprovals
TYCO TY1231 Pendent / Recessed Pendent Sprinkler, K2.8, 1/2″ NPT — TY-FRB2.8Quick ResponseUL · C-UL · FM · LPCB · VdS (per Tables A–D)
TYCO TY2131 Upright Sprinkler, K4.2, 1/2″ NPT — TY-FRB4.2Quick ResponseUL · C-UL · FM · LPCB · VdS (per Tables A–D)
TYCO TY2231 Pendent / Recessed Pendent Sprinkler, K4.2, 1/2″ NPT — TY-FRB4.2Quick ResponseUL · C-UL · FM · LPCB · VdS (per Tables A–D)
TYCO TY3131 Upright Sprinkler, K5.6, 1/2″ NPT — TY-FRB5.6Quick ResponseUL · C-UL · FM · LPCB · VdS (per Tables A–D)
TYCO TY3231 Pendent / Recessed Pendent Sprinkler, K5.6, 1/2″ NPT — TY-FRB5.6Quick ResponseUL · C-UL · FM · LPCB · VdS (per Tables A–D)
TYCO TY4131 Upright Sprinkler, K8.0, 3/4″ NPT — TY-FRB8.0Quick ResponseUL · C-UL · FM · LPCB · VdS (per Tables A–D)
TYCO TY4231 Pendent / Recessed Pendent Sprinkler, K8.0, 3/4″ NPT — TY-FRB8.0Quick ResponseUL · C-UL · FM · LPCB · VdS (per Tables A–D)
TYCO TY4831 Upright Sprinkler, K8.0, 1/2″ NPT — TY-FRB8.0Quick ResponseUL · C-UL · FM · LPCB · VdS (per Tables A–D)
TYCO TY4931 Pendent Sprinkler, K8.0, 1/2″ NPT — TY-FRB8.0Quick ResponseUL · C-UL · FM · LPCB · VdS (per Tables A–D)