Skip to content
Exclusive agent of MECH products in Saudi Arabia
Store Request a quote

MECH WAFER CHECK VALVE ANSI UL/FM RED

Model DH77XSR

Connection ends
ASME B16.1 CL125, ASME B16.5 CL150
Working pressure
300 PSI
Coating
FBE — ANSI/AWWA C550
Sizes
2" – 16" (DN50 – DN400)
Request a quote for this product
Or buy from the online store
SIZES & DIMENSIONS

Sizes & dimensions

SizeDNL Length (mm)D (mm)D1 (mm)D2 (mm)
2"DN50541066846
2.5"DN65601277860
3"DN805713410270
4"DN1006716211784
5"DN12583194145115
6"DN15095218170134
8"DN200127277226184
10"DN250140336265220
12"DN300181406310260
14"DN350184447360302
16"DN400191505410350
PROJECT APPROVALS

Approved on projects

98 projects and 61 owners approved this product or its family through the project consultants.

and 86 more projects.

Original approval letters are provided on request with your submittal.

The MECH wafer check valve ansi ul/fm red, sizes 2″ – 16″ (DN50 – DN400), working pressure 300 PSI. It lets water flow one way and stops it flowing back. This guide explains what it does and how it works, related models, technical data, the critical point in selection and installation, and common mistakes. For more, read the guide check valves in fire protection.

At a glance

  • A check valve opens under flow in the right direction and closes automatically when flow stops or reverses, preventing backflow from the system to the supply or from one pump into another.
  • Sizes 2″ – 16″ (DN50 – DN400).
  • Working pressure 300 PSI.
  • Connection: ASME B16.1 CL125, ASME B16.5 CL150.

Check valve: what it does and how it works

A check valve opens under flow in the right direction and closes automatically when flow stops or reverses, preventing backflow from the system to the supply or from one pump into another.

The swing type has a clapper hinged on a pin; the wafer type is slim and fits between two flanges to save space. It is used on fire pump discharges, fire department connections and network supplies.

Related models

check valve family
ModelProductSizesPressureApprovals
WAFER CHECK VALVE ANSI UL/FM RED — this productWAFER CHECK VALVE ANSI UL/FM RED2″ – 16″ (DN50 – DN400)300 PSI—
H84XSWING CHECK VALVE GROOVED RED2″ – 12″ (DN50 – DN300)300 / 363 PSIUL / FM / LPCB
H44X2SWING CHECK VALVE FLANGE RED UL/FM2″ – 12″ (DN50 – DN300)300 / 363 PSIUL / FM / LPCB

Technical data

Specification of the product
ItemSpecification
Connection endsASME B16.1 CL125, ASME B16.5 CL150
Working pressure300 PSI
CoatingFBE — ANSI/AWWA C550
Sizes2″ – 16″ (DN50 – DN400)

Dimensions for every size are in the size table at the top of the page.

Direction and orientation

The arrow on the body must point with the flow, and the orientation (horizontal or vertical with upward flow) must be within what the model’s listing and datasheet allow.

Caution

Do not fit a check valve directly after an elbow or pump without the recommended straight run, as turbulence makes the clapper chatter and wear.

Installation steps

  1. Check the arrow points with the flow.
  2. Install in a listed orientation, with enough straight pipe upstream.
  3. For wafer type: make sure the disc moves freely within the adjacent flanges.
  4. Test closure after commissioning.

Common mistakes

  • Installing it against the flow.
  • Fitting it right after an elbow or pump so it chatters.
  • Vertical downward-flow installation that is not allowed.

Files and ordering

On this page: Product datasheet, MECH Fire Protection Valves Catalogue (UL/FM), Material Safety Data Sheet (MSDS). Add the product to your request list with size and quantity and we send a quotation, or build a submittal PDF for the consultant. Fu-Mech is the exclusive MECH agent in Saudi Arabia.

Frequently asked questions

What is the difference between swing and wafer types?

A swing check has a hinged clapper and is easy to inspect; a wafer check is slimmer and fits between two flanges. See check valves.

Where is it installed in a fire system?

On fire pump discharges, the fire department connection and network supplies, per the design.

What is the working pressure?

300 PSI per the product data. The pressure for each size or listed model is in the size table and datasheet.

Is it UL / FM approved?

No approvals are listed for this model in the product data. If your project needs a specific approval, ask us before ordering.

What end connection does it have?

ASME B16.1 CL125, ASME B16.5 CL150. Choose the connection that matches the adjacent pipe and fittings.

References

  • ASME B16.1 — Gray Iron Pipe Flanges and Flanged Fittings
  • ASME B16.5 — Pipe Flanges and Flanged Fittings
  • AWWA C550 — Protective Interior Coatings for Valves and Hydrants
  • MECH catalogue — Fire fighting valves

This guide is general information to help with selection. Figures come from the product data on this page and the MECH catalogue; final design is by the project’s approved designer to the applicable standards and the project specification.