Skip to content
Exclusive agent of MECH products in Saudi Arabia
Store Request a quote

MECH Y.STRAINER VALVE FLANGED UL/FM RED MODEL V4

Model V4

Connection ends
Flange ASME B16.1 CL125
Working pressure
300 PSI
Temperature
0 – 80 °C
Coating
FBE — ANSI/AWWA C550
Approvals
UL Listed
Sizes
2" – 12" (DN50 – DN300)
Request a quote for this product
Or buy from the online store
SIZES & DIMENSIONS

Sizes & dimensions

SizeDNL Length (mm)D Flange diameter (mm)D1 Bolt circle (mm)b Flange thickness (mm)n-Φd Bolt holesH Height (mm)
2"DN50200152120.5164-Φ19.1155
2.5"DN65254178139.517.54-Φ19.1165
3"DN80257191152.5194-Φ19.1180
4"DN100308229190.5248-Φ19.1229
5"DN125397254216248-Φ22.2285
6"DN150470279241.525.58-Φ22.2311
8"DN200549343298.528.58-Φ22.2394
10"DN25065440636230.512-Φ25.4487
12"DN3007594834323212-Φ25.4547
PROJECT APPROVALS

Approved on projects

98 projects and 61 owners approved this product or its family through the project consultants.

and 86 more projects.

Original approval letters are provided on request with your submittal.

The MECH y.strainer valve flanged ul/fm red, model V4, sizes 2″ – 12″ (DN50 – DN300), working pressure 300 PSI, UL Listed approved. It traps debris ahead of pumps, valves and sensitive devices. This guide explains what it does and how it works, related models, technical data, the critical point in selection and installation, and common mistakes. For more, read the guide Y-strainers.

At a glance

  • A Y-strainer passes water through a metal screen inside an angled Y-shaped leg, trapping stones, rust and debris to protect the equipment downstream.
  • Sizes 2″ – 12″ (DN50 – DN300).
  • Working pressure 300 PSI.
  • Approvals: UL Listed.
  • Connection: Flange ASME B16.1 CL125.
  • Operating temperature: 0 – 80 °C.

Y-strainer: what it does and how it works

A Y-strainer passes water through a metal screen inside an angled Y-shaped leg, trapping stones, rust and debris to protect the equipment downstream.

The screen is cleaned through the leg cover without removing the line; some strainers have a blow-off tapping for quick cleaning.

Technical data

Specification of model V4
ItemSpecification
Connection endsFlange ASME B16.1 CL125
Working pressure300 PSI
Temperature0 – 80 °C
CoatingFBE — ANSI/AWWA C550
ApprovalsUL Listed
Sizes2″ – 12″ (DN50 – DN300)

Dimensions for every size are in the size table at the top of the page.

Leg orientation and cleaning

On horizontal lines the leg points downward so debris collects in it. Leave room to remove the cover and withdraw the screen, and fit isolating valves for cleaning.

Caution

A blocked strainer chokes flow and weakens system performance; inspect and clean it regularly per the maintenance programme.

Installation steps

  1. Install with the arrow in the direction of flow.
  2. Point the leg downward on horizontal lines.
  3. Leave room to withdraw the screen and fit isolating valves on both sides.
  4. Clean the screen after the first system flush.

Common mistakes

  • Leg pointing upward so debris does not collect.
  • No room left to remove the cover.
  • Skipping the clean after the first flush.

Files and ordering

On this page: Product datasheet, Installation & operation manual, MECH Fire Protection Valves Catalogue (UL/FM), Material Safety Data Sheet (MSDS). Add the product to your request list with size and quantity and we send a quotation, or build a submittal PDF for the consultant. Fu-Mech is the exclusive MECH agent in Saudi Arabia.

Frequently asked questions

Where should I install the strainer?

Upstream of pumps, valves, meters and control devices that debris can affect. See Y-strainers.

How do I clean it?

Isolate the strainer, remove the leg cover, withdraw and wash the screen, then refit it.

What is the working pressure of model V4?

300 PSI per the product data. The pressure for each size or listed model is in the size table and datasheet.

What approvals does it carry?

UL Listed per the product data. Check the size and listed model in the approval listings, and see how to verify UL and FM approvals.

What end connection does it have?

Flange ASME B16.1 CL125. Choose the connection that matches the adjacent pipe and fittings.

References

  • ASME B16.1 — Gray Iron Pipe Flanges and Flanged Fittings
  • AWWA C550 — Protective Interior Coatings for Valves and Hydrants
  • MECH catalogue — Fire fighting valves

This guide is general information to help with selection. Figures come from the product data on this page and the MECH catalogue; final design is by the project’s approved designer to the applicable standards and the project specification.