The MECH grooved red ecc, model 230, in ductile iron, sizes 1-1/2″ × 1-1/4″ – 24″ × 20″ (DN40×32 – DN600×500), working pressure up to 500 PSI depending on size, UL / FM approved depending on size. This guide explains what it does and how it works, compares it with related models, and covers technical data, the critical point in selection and installation, and common mistakes. For more, read the technical library guide.
At a glance
- An eccentric reducer has one flat side, so the two ends are offset.
- Sizes 1-1/2″ × 1-1/4″ – 24″ × 20″ (DN40×32 – DN600×500) — working pressure up to 500 PSI depending on size.
- Approvals: UL / FM (vary by size).
- Material Ductile iron ASTM A536 Gr. 65-45-12.
- Designed to ASTM F1548, AWWA C606, ISO 6182-12.
What is a grooved eccentric reducer and how does it work?
An eccentric reducer has one flat side, so the two ends are offset. The large end is grooved; the small end is grooved or female-threaded depending on the model.
Its key use is on horizontal pump suction lines: fitted flat side up, the top of the pipe stays level up to the pump inlet and no air pocket forms.
Models in the same family
| Model | Item | Sizes | Max pressure | Approvals |
|---|---|---|---|---|
| 230N | MECH GROOVED ECCENTRIC REDUCER (THD) | 4″ × 2-1/2″ – 6″ × 3″ | 300 PSI | UL / FM |
| 230 — this product | MECH GROOVED RED ECC | 1-1/2″ × 1-1/4″ – 24″ × 20″ | 500 PSI | UL / FM |
Technical data
| Item | Specification |
|---|---|
| Design standard | ASTM F1548, AWWA C606, ISO 6182-12 |
| Material | Ductile iron ASTM A536 Gr. 65-45-12 |
| Coating | Electrophoretic (std.) — epoxy / hot-dip galvanized optional |
| Sizes | 1-1/2″ × 1-1/4″ – 24″ × 20″ (DN40×32 – DN600×500) |
| Approvals | Sizes | Working pressure |
|---|---|---|
| Not stated in the table | 1-1/2″ × 1-1/4″ – 24″ × 20″ | 300–500 PSI |
| UL / FM | 3″ × 2″ – 10″ × 8″ | 300–500 PSI |
Some sizes come in two pipe outside diameters (for example 73.0 and 76.1 mm for 2-1/2″) depending on the pipe standard; select by the actual outside diameter of your project pipe.
Full dimensions for every size (bolts and more) are in the size table at the top of the page.
Fitting orientation
Fitted upside down (flat side down) on a horizontal suction it leaves a pocket at the top where air collects and passes into the pump, causing cavitation and poor performance.
Caution
This is established pump-suction piping practice; the approved designer’s details govern.
Installation steps
- Check that the pipe ends are grooved to the right dimensions to AWWA C606 (roll or cut groove) and are free of burrs, rust and dirt.
- Inspect the gasket and lubricate its outside and lips with the lubricant recommended in the MECH catalogue; never use petroleum-based products with an EPDM gasket.
- Fit the gasket over one pipe end, bring the other end or the fitting into place, and slide the gasket so it is centred between the two grooves.
- Place both housing halves over the gasket so their keys engage the grooves on both sides.
- Hand-tighten the nuts first, making sure each oval-neck bolt sits in its hole, then tighten alternately and evenly to the torque in the MECH installation manual — never exceed it.
The fitting joins with grooved couplings; how the joint is finished (even pad gap or pads meeting) follows the coupling type in the MECH manual.
Full details and bolt torques are in the MECH installation manual among the files on this page.
Common mistakes
- Letting the gasket lip overhang the pipe end or protrude into a groove, so the gasket is not centred on the joint.
- Exceeding the specified bolt torque, which can damage the bolt or the joint.
- Grooves that do not meet AWWA C606 dimensions, or pipe ends that are not square.
- Tightening the nuts on one side only, so the housing tilts and the key does not seat in the groove.
- Using petroleum-based lubricant that damages the EPDM gasket.
Files and ordering
On this page: Product page (catalogue), Product page (catalogue), MECH Grooved Fittings & Couplings Catalogue, Installation & operation manual, Material Safety Data Sheet (MSDS). Add the product to your request list with size and quantity and we send a quotation, or build a submittal PDF for the consultant. Fu-Mech is the exclusive MECH agent in Saudi Arabia.
Frequently asked questions
Why is the flat side up?
So that no air collects at the top of the suction line ahead of the pump.
What is the maximum working pressure of model 230?
Up to 500 PSI depending on size (from 300 to 500). The pressure for each size is in the size table.
Is model 230 UL / FM approved?
Yes. Approvals by size: — for 1-1/2″ × 1-1/4″ – 24″ × 20″; UL / FM for 3″ × 2″ – 10″ × 8″. See the size table on this page and the guide how to verify UL and FM approvals.
What is the gasket material, and does it suit all fluids?
Gasket type and suitable services are given in the MECH catalogue.
Does it suit roll-grooved and cut-grooved pipe?
Grooves are to AWWA C606, rolled or cut; what matters is correct groove dimensions. The difference is explained in the guide roll grooving vs cut grooving.
References
- ASTM F1548 — Standard Specification for Performance of Fittings for Use with Gasketed Mechanical Couplings Used in Piping Applications
- AWWA C606 — Grooved and Shouldered Joints
- ISO 6182-12 — Fire protection — Automatic sprinkler systems — Requirements and test methods for grooved-end components for steel pipe systems
- ASTM A536 — Standard Specification for Ductile Iron Castings
- UL 213 — Rubber Gasketed Fittings for Fire-Protection Service
- FM 1920 — Approval Standard for Pipe Couplings and Fittings for Fire Protection Systems
- MECH catalogue — Grooved Fittings & Couplings — and installation manual
This guide is general information to help with selection. Figures come from the product data on this page and the MECH catalogue; final design is by the project’s approved designer to NFPA 13 and the project specification.