Skip to content
Exclusive agent of MECH products in Saudi Arabia
Store Request a quote

TEST & DRAIN VALVE | Model: Y-4030

Model Y-4030

Design standard
FM1625, UL258
Connection ends
ASME B1.20.1
Working pressure
300 PSI
Temperature
0 – 80 °C
Orifice
K-5.6
Sizes
1" – 2" (DN25 – DN50)
Request a quote for this product
Or buy from the online store
SIZES & DIMENSIONS

Sizes & dimensions

SizeDNL (mm)H (mm)A (mm)G Thread
1"DN25134.563.5130BSPT 1"/NPT 1"
1-1/4"DN32135.564.5132.5BSPT 1-1/4"/NPT 1-1/4"
1-1/2"DN40163.579152BSPT 1-1/2"/NPT 1-1/2"
2"DN5016779152BSPT 2"/NPT 2"
PROJECT APPROVALS

Approved on projects

98 projects and 61 owners approved this product or its family through the project consultants.

and 86 more projects.

Original approval letters are provided on request with your submittal.

The MECH test & drain valve, model Y-4030, sizes 1″ – 2″ (DN25 – DN50), working pressure 300 PSI. It combines alarm testing and system draining in one valve with a sprinkler-equivalent test orifice. This guide explains what it does and how it works, related models, technical data, the critical point in selection and installation, and common mistakes.

At a glance

  • A test and drain valve has three positions: off, test and drain.
  • Sizes 1″ – 2″ (DN25 – DN50).
  • Working pressure 300 PSI.
  • Connection: ASME B1.20.1.
  • Operating temperature: 0 – 80 °C.

Test and drain valve: what it does and how it works

A test and drain valve has three positions: off, test and drain. In test it passes water through an orifice with the K-factor of one sprinkler (K-5.6 per the product data), simulating an open sprinkler to test the flow switch and alarm; in drain it empties the system.

It has a sight glass to see the flow during testing and is normally fitted after the flow indicator on each floor or zone.

Technical data

Specification of model Y-4030
ItemSpecification
Design standardFM1625, UL258
Connection endsASME B1.20.1
Working pressure300 PSI
Temperature0 – 80 °C
OrificeK-5.6
Sizes1″ – 2″ (DN25 – DN50)

Dimensions for every size are in the size table at the top of the page.

Test orifice

The test orifice must match the smallest sprinkler K-factor in the zone so the test represents one sprinkler opening.

Caution

Pipe the drain to a point that can take the full flow.

Installation steps

  1. Install after the flow indicator with the arrow in the direction of flow.
  2. Pipe the drain to a suitable outlet.
  3. Test the alarm in the test position, watching the sight glass.
  4. Return the handle to off after testing.

Common mistakes

  • A test orifice larger than the sprinkler K-factor.
  • Draining to a point that cannot take the flow.
  • Leaving the handle in test.

Files and ordering

On this page: Product datasheet, Installation & operation manual, MECH Fire Protection Valves Catalogue (UL/FM). Add the product to your request list with size and quantity and we send a quotation, or build a submittal PDF for the consultant. Fu-Mech is the exclusive MECH agent in Saudi Arabia.

Frequently asked questions

Why a K-5.6 test orifice?

To simulate the flow of one K5.6 sprinkler, the common standard sprinkler K-factor.

Where is it installed?

After the flow indicator on each floor or zone.

What is the working pressure of model Y-4030?

300 PSI per the product data. The pressure for each size or listed model is in the size table and datasheet.

Is it UL / FM approved?

No approvals are listed for this model in the product data. If your project needs a specific approval, ask us before ordering.

What end connection does it have?

ASME B1.20.1. Choose the connection that matches the adjacent pipe and fittings.

References

  • ASME B1.20.1 — Pipe Threads, General Purpose, Inch (NPT)
  • MECH catalogue — Product datasheet

This guide is general information to help with selection. Figures come from the product data on this page and the MECH catalogue; final design is by the project’s approved designer to the applicable standards and the project specification.