The TYCO 12 Sprinkler Cabinet is a metal enclosure with a hinged cover for on-site storage of an emergency supply of sprinklers and a sprinkler wrench. NFPA 13 requires a representative number of each sprinkler type used in the system to be stored on site in a cabinet, so operated or damaged sprinklers can be replaced immediately. This cabinet holds 12 1/2″ and 3/4″ NPT sprinklers. See the complete guide to sprinkler systems in Saudi Arabia.
In short
- Capacity: 12 — 1/2″ and 3/4″ NPT sprinklers.
- Heavy-gauge steel in red enamel, with knock-outs for sprinkler sizes.
- Weight: 1.81 kg.
- Installed at or near the system control valve.
How many spare sprinklers are needed?
Per Table A of the datasheet: under 300 sprinklers in the system → 6 spares; 300 – 1000 → 12; over 1000 → 24. The stock includes each type and temperature rating used in the system.
The cabinet must also contain a sprinkler wrench of the appropriate type for the stored sprinklers.
Models in the datasheet
| Cabinet | Holds |
|---|---|
| 6 Sprinkler Cabinet | 1/2″ and 3/4″ NPT sprinklers |
| 12 Sprinkler Cabinet — this model | 1/2″ and 3/4″ NPT sprinklers |
| 6 ESFR Sprinkler Cabinet | ESFR sprinklers, 3/4″ and 1″ NPT |
| 6 ESFR-34 Sprinkler Cabinet | ESFR-34 sprinklers, 3/4″, 1″ and 1-1/4″ NPT |
Links to the other models are in the “Similar models” table below.
Technical data
| Item | Value |
|---|---|
| Model | 12 Sprinkler Cabinet |
| Capacity | 12 |
| Holds | 1/2″ and 3/4″ NPT sprinklers |
| Material | Carbon steel, red enamel |
| Weight | 1.81 kg |
| Part number | P/N 1124 |
The critical point: the right stock
The cabinet alone is not enough: it must hold the required number of each type and temperature rating installed, and the right wrench. It must not be located above 38°C or in a corrosive atmosphere.
Installation steps
- Mount the cabinet on the wall through its two 3/16″ holes, or to the system riser with a strap hanger.
- Locate it at or near the system control valve, readily accessible.
- Open the knock-outs needed for the sprinkler sizes with a screwdriver from the top of the shelf.
- Stock sprinklers by the installed types and ratings and the quantity in Table A, with the wrench.
Common mistakes
- Stocking only one sprinkler type when the system has several types and ratings.
- Leaving out the sprinkler wrench.
- Placing the cabinet in a hot area or far from the control valve.
Inspection and maintenance
Per the datasheet, inspect the cabinet, wrench and stock at least quarterly: accessible location, no corrosive atmosphere or temperature above 38°C, enough of each type and rating, sprinklers in good condition, and the right wrench present.
Files and ordering
TYCO datasheet TFP785 and the available approval certificates are in the files section of this page. When ordering, state the cabinet size 12 Sprinkler Cabinet (P/N 1124). The datasheet lists the part numbers (P/N).
How to order
Use the “Build your order” section on this page: add every model and quantity, then send the whole order by email or WhatsApp. It reaches us as a tidy PDF request sheet and we contact you with the quotation.
FAQ
Are sprinklers and wrench included?
No, the cabinet is ordered on its own; sprinklers and wrench are ordered to suit the system.
Which size do I choose?
From the required number of spares (Table A) and their type: standard cabinets for 1/2″ and 3/4″ sprinklers, ESFR cabinets for larger ones.
How often is it inspected?
At least quarterly, per the datasheet.
References
- TYCO TFP785 — Datasheet (attached)
- NFPA 13 — Standard for the Installation of Sprinkler Systems
- NFPA 25 — Inspection, Testing and Maintenance of Water-Based Fire Protection Systems