The TYCO TY3211 is the pendent / recessed pendent model of the TY-L series, with a K 5.6 discharge coefficient and 1/2″ NPT thread, standard response and standard coverage, operated by a solder-type element. It is designed for light, ordinary and extra-hazard occupancies such as banks, hotels, shopping malls, factories, refineries and chemical plants. Installed hanging below the pipe; it can also be recessed into a finished ceiling with its specified recessed escutcheon. For where the sprinkler sits in the whole system, see the complete guide to sprinkler systems in Saudi Arabia.
In short
- Model (SIN): TY3211 — Pendent / Recessed Pendent.
- Discharge coefficient K 5.6, 1/2″ NPT connection.
- Solder-type element, standard response.
- Temperature ratings in the datasheet: 74°C / 100°C / 138°C.
- Maximum working pressure: 175 psi (12.1 bar).
- Series approvals: UL, C-UL, FM, EAC. The approval of each model, finish and rating is in the approvals table of datasheet TFP110.
How this sprinkler works
A copper tube sealed by two stainless steel balls holds a fusible alloy. When the rated temperature is reached the alloy melts, the balls are forced toward each other and the tension mechanism releases, letting the sprinkler operate.
Installed hanging below the pipe; it can also be recessed into a finished ceiling with its specified recessed escutcheon. Standard response is typically used for storage and industrial areas, per the project design.
Models in the series
| SIN | Orientation | K-factor | Thread |
|---|---|---|---|
| TY3111 | Upright | 5.6 | 1/2″ NPT |
| TY3211 — this model | Pendent / Recessed Pendent | 5.6 | 1/2″ NPT |
| TY4111 | Upright | 8.0 | 3/4″ NPT |
| TY4811 | Upright | 8.0 | 1/2″ NPT |
Links to the other models are in the “Similar models” table below. The choice of model comes from the hydraulic calculation, hazard classification and installation method in the project design.
Application notes
- A solder-type sprinkler rather than a bulb type; an intermediate-level version of the pendent is described in the datasheet.
- Wax-coated sprinklers are tightened with an adjustable wrench taking care not to damage the wax; retouching with a heated rod is permitted only at initial installation.
Technical data
| Item | Value |
|---|---|
| Model (SIN) | TY3211 |
| Orientation | Pendent / Recessed Pendent |
| Discharge coefficient | K 5.6 gpm/psi½ (80.6 L/min/bar½) |
| Thread | 1/2″ NPT |
| Element and response | Solder-type element — Standard Response |
| Coverage | Standard Coverage |
| Temperature ratings | 74°C / 100°C / 138°C |
| Maximum working pressure | 175 psi (12.1 bar) |
| Installation torque | 7 – 14 lb-ft (9.5 – 19.0 N·m) |
| Wrench | W-Type 9 |
| Escutcheon | Recessed pendent: Style 20 recessed escutcheon only |
| Approvals | UL, C-UL, FM, EAC |
| Datasheet | TYCO TFP110 |
The critical point: wrench and torque
Tighten only with the W-Type 9 wrench on the wrenching area, within the torque for its thread. Higher torque can distort the inlet and cause leakage or impairment.
A wax-coated 138°C sprinkler takes the same maximum ceiling temperature as the 100°C sprinkler, which is 65°C.
Installation steps
- Install the sprinkler in its correct orientation (Pendent / Recessed Pendent) as shown in the datasheet — never reversed.
- Apply pipe-thread sealant to the threads, then hand-tighten the sprinkler.
- Finish with the specified wrench (W-Type 9) within 7 – 14 lb-ft (9.5 – 19.0 N·m). Higher torque can distort the inlet and cause leakage.
- With an escutcheon, use only the specified one (Recessed pendent: Style 20 recessed escutcheon only) and never compensate for adjustment by changing the torque.
Common mistakes
- Compensating for too little recessed escutcheon adjustment by under- or over-tightening instead of readjusting the fitting.
- Installing a sprinkler that was dropped, struck or slipped by the wrench. The datasheet requires any such sprinkler to be replaced.
- Painting or coating sprinklers on site. Sprinklers must not be altered after leaving the factory; altered sprinklers are replaced.
- Hanging objects from sprinklers, or cleaning them with anything other than a gentle feather duster.
Maintenance
Sprinklers that leak or show visible corrosion must be replaced, as must sprinklers exposed to corrosive products of combustion that cannot be fully cleaned. The owner is responsible for inspection, testing and maintenance to NFPA 25 and the authority having jurisdiction, preferably by a qualified inspection service. Before closing a main control valve for maintenance, obtain permission from the proper authorities and notify everyone affected.
Files and ordering
TYCO datasheet TFP110 and the available approval certificates are in the files section of this page. When ordering, state the model TY3211, temperature rating and finish, escutcheon. The datasheet lists the part numbers (P/N) for each combination.
How to order
Use the “Build your order” section on this page: add every model and quantity, then send the whole order by email or WhatsApp. It reaches us as a tidy PDF request sheet and we contact you with the quotation.
FAQ
What does TY3211 mean?
It is TYCO’s Sprinkler Identification Number (SIN). It identifies the exact model — orientation, K-factor and thread. The sprinkler is ordered by this number together with temperature rating and finish.
How do I choose the temperature rating?
From the highest expected ceiling temperature and the rating classes in the project’s governing standard, within the ratings available for this model in the datasheet.
Do all models in the series carry the same approvals?
Not always. The approvals table in datasheet TFP110 gives each model’s approvals by rating and finish, so check it when the project requires a specific approval.
References
- TYCO TFP110 — Series datasheet (attached)
- NFPA 13 — Standard for the Installation of Sprinkler Systems
- NFPA 25 — Inspection, Testing and Maintenance of Water-Based Fire Protection Systems
- TYCO TFP700 — Installer warning for handling and installing sprinklers
This page is general information to help with selection and ordering, taken from the attached TYCO datasheet. Final design is set by the project’s approved designer; the project specification, the consultant’s drawings and the latest datasheet revision govern.