TYCO TY3431 Vertical Sidewall Sprinkler, K5.6, 1/2″ NPT — TY-FRB

Model TY3431

Brand
TYCO
Model
TY3431
Series
TY-FRB
Orientation
Vertical Sidewall
K-factor
5.6 gpm/psi½
Thread connection
1/2" NPT
Response
Quick Response
Coverage
Standard Coverage
Temperature ratings
57 / 68 / 79 / 93 / 141 °C
Max. working pressure
175 psi (12.1 bar); 250 psi (17.2 bar) under UL
Approvals
UL · C-UL · FM · LPCB · NYC (per Table A)
Datasheet
TFP176
Request a quote for this product
Or buy from the online store

The TYCO TY3431 is the vertical sidewall model of the TY-FRB series, with a K 5.6 discharge coefficient and 1/2″ NPT thread, quick response and standard coverage, operated by a glass bulb 3 mm. It is designed for light and ordinary hazard commercial occupancies such as banks, hotels and shopping malls. Installed vertically along a wall just below the ceiling, throwing water into the room. For where the sprinkler sits in the whole system, see the complete guide to sprinkler systems in Saudi Arabia.

In short

  • Model (SIN): TY3431 — Vertical Sidewall.
  • Discharge coefficient K 5.6, 1/2″ NPT connection.
  • Glass bulb 3 mm, quick response.
  • Temperature ratings in the datasheet: 57 / 68 / 79 / 93 / 141 °C.
  • Maximum working pressure: 175 psi (12.1 bar); 250 psi (17.2 bar) under UL.
  • Series approvals: UL, C-UL, FM, LPCB, NYC (per Table A). The approval of each model, finish and rating is in the approvals table of datasheet TFP176.

How this sprinkler works

The glass bulb contains a fluid that expands when exposed to heat. When the rated temperature is reached, the fluid expands enough to shatter the bulb, the sprinkler opens and the deflector spreads the water over the fire area.

Installed vertically along a wall just below the ceiling, throwing water into the room. Quick response means the thermal element reacts faster, so the sprinkler operates earlier than a standard-response sprinkler of the same rating.

Models in the series

Models in datasheet TFP176
SINOrientationK-factorThread
TY3331Horizontal Sidewall5.61/2″ NPT
TY3431 — this modelVertical Sidewall5.61/2″ NPT

Links to the other models are in the “Similar models” table below. The choice of model comes from the hydraulic calculation, hazard classification and installation method in the project design.

Application notes

  • Quick response with a 3 mm bulb. Sidewall sprinklers are used instead of pendents or uprights where piping across the ceiling is not wanted.
  • Corrosion-resistant finishes are available per the datasheet for corrosive atmospheres; the datasheet notes that corrosion tests do not represent every possible atmosphere, so suitability for the actual environment should be checked.

Technical data

Technical data — TY3431 per TYCO datasheet TFP176
ItemValue
Model (SIN)TY3431
OrientationVertical Sidewall
Discharge coefficientK 5.6 gpm/psi½ (80.6 L/min/bar½)
Thread1/2″ NPT
Element and responseGlass bulb 3 mm — Quick Response
CoverageStandard Coverage
Temperature ratings57 / 68 / 79 / 93 / 141 °C
Maximum working pressure175 psi (12.1 bar); 250 psi (17.2 bar) under UL
Installation torque7 – 14 lb-ft (9.5 – 19.0 N·m)
WrenchW-Type 6 (W-Type 7 for recessed)
EscutcheonRecessed horizontal sidewall: Style 10 or Style 20 only
ApprovalsUL, C-UL, FM, LPCB, NYC (per Table A)
DatasheetTYCO TFP176

The critical point: orientation and torque

The deflector orientation sets the throw direction, so install as shown in the datasheet, tightening with the W-Type 6 wrench at 7 – 14 lb-ft.

Installation steps

  1. Inspect before installing: never install a sprinkler whose bulb is cracked or has lost liquid.
  2. Install the sprinkler in its correct orientation (Vertical Sidewall) as shown in the datasheet — never reversed.
  3. Apply pipe-thread sealant to the threads, then hand-tighten the sprinkler.
  4. Finish with the specified wrench (W-Type 6 (W-Type 7 for recessed)) within 7 – 14 lb-ft (9.5 – 19.0 N·m). Higher torque can distort the inlet and cause leakage.

Common mistakes

  • Installing a sprinkler that was dropped, struck or slipped by the wrench. The datasheet requires any such sprinkler to be replaced.
  • Painting or coating sprinklers on site. Sprinklers must not be altered after leaving the factory; altered sprinklers are replaced.
  • Hanging objects from sprinklers, or cleaning them with anything other than a gentle feather duster.

Maintenance

Sprinklers that leak or show visible corrosion must be replaced, as must sprinklers exposed to corrosive products of combustion that cannot be fully cleaned. The owner is responsible for inspection, testing and maintenance to NFPA 25 and the authority having jurisdiction, preferably by a qualified inspection service. Before closing a main control valve for maintenance, obtain permission from the proper authorities and notify everyone affected.

Files and ordering

TYCO datasheet TFP176 and the available approval certificates are in the files section of this page. When ordering, state the model TY3431, temperature rating and finish, escutcheon. The datasheet lists the part numbers (P/N) for each combination.

How to order

Use the “Build your order” section on this page: add every model and quantity, then send the whole order by email or WhatsApp. It reaches us as a tidy PDF request sheet and we contact you with the quotation.

FAQ

What does TY3431 mean?

It is TYCO’s Sprinkler Identification Number (SIN). It identifies the exact model — orientation, K-factor and thread. The sprinkler is ordered by this number together with temperature rating and finish.

How do I choose the temperature rating?

From the highest expected ceiling temperature and the rating classes in the project’s governing standard, within the ratings available for this model in the datasheet.

Do all models in the series carry the same approvals?

Not always. The approvals table in datasheet TFP176 gives each model’s approvals by rating and finish, so check it when the project requires a specific approval.

What is the benefit of quick response?

The thermal element reacts faster, so the sprinkler operates earlier and limits heat and smoke spread; standards require it in some occupancies such as light hazard.

References

  • TYCO TFP176 — Series datasheet (attached)
  • NFPA 13 — Standard for the Installation of Sprinkler Systems
  • NFPA 25 — Inspection, Testing and Maintenance of Water-Based Fire Protection Systems
  • TYCO TFP700 — Installer warning for handling and installing sprinklers

This page is general information to help with selection and ordering, taken from the attached TYCO datasheet. Final design is set by the project’s approved designer; the project specification, the consultant’s drawings and the latest datasheet revision govern.