TYCO TY3488 Window Pendent Vertical Sidewall Sprinkler, K5.6, 1/2″ NPT — WS Window

Model TY3488

Brand
TYCO
Model
TY3488
Series
WS Window
Orientation
Window Pendent Vertical Sidewall
K-factor
5.6 gpm/psi½
Thread connection
1/2" NPT
Response
Quick Response
Coverage
Specific application window sprinkler
Temperature ratings
68 / 93 °C
Max. working pressure
Horizontal sidewall 70 psi (cold solder limit), 175 psi with a baffle
Approvals
UL · C-UL · NYC
Datasheet
TFP620
Request a quote for this product
Or buy from the online store

The TYCO TY3488 is the window pendent vertical sidewall model of the WS Window series, with a K 5.6 discharge coefficient and 1/2″ NPT thread, quick response and specific application window sprinkler, operated by a glass bulb. It is designed for protecting heat-strengthened, tempered or ceramic glass windows with closed sprinklers, as fire tested to the ASTM E119 time/temperature curve. Installed pendent with its centreline parallel to the glass surface. For where the sprinkler sits in the whole system, see the complete guide to sprinkler systems in Saudi Arabia.

In short

  • Model (SIN): TY3488 — Window Pendent Vertical Sidewall.
  • Discharge coefficient K 5.6, 1/2″ NPT connection.
  • Glass bulb, quick response.
  • Temperature ratings in the datasheet: 68 / 93 °C.
  • Maximum working pressure: Horizontal sidewall 70 psi (cold solder limit), 175 psi with a baffle.
  • Series approvals: UL, C-UL, NYC. The approval of each model, finish and rating is in the approvals table of datasheet TFP620.

How this sprinkler works

The glass bulb contains a fluid that expands when exposed to heat. When the rated temperature is reached, the fluid expands enough to shatter the bulb, the sprinkler opens and the deflector spreads the water over the fire area.

Installed pendent with its centreline parallel to the glass surface. Quick response means the thermal element reacts faster, so the sprinkler operates earlier than a standard-response sprinkler of the same rating.

Models in the series

Models in datasheet TFP620
SINOrientationK-factorThread
TY3388Window Horizontal Sidewall5.61/2″ NPT
TY3488 — this modelWindow Pendent Vertical Sidewall5.61/2″ NPT

Links to the other models are in the “Similar models” table below. The choice of model comes from the hydraulic calculation, hazard classification and installation method in the project design.

Application notes

  • The first sprinklers specifically listed to provide complete wetting and coverage of windows using closed sprinklers.

Technical data

Technical data — TY3488 per TYCO datasheet TFP620
ItemValue
Model (SIN)TY3488
OrientationWindow Pendent Vertical Sidewall
Discharge coefficientK 5.6 gpm/psi½ (80.6 L/min/bar½)
Thread1/2″ NPT
Element and responseGlass bulb — Quick Response
CoverageSpecific application window sprinkler
Temperature ratings68 / 93 °C
Maximum working pressureHorizontal sidewall 70 psi (cold solder limit), 175 psi with a baffle
Installation torque7 – 14 lb-ft (9.5 – 19.0 N·m)
WrenchW-Type 20
ApprovalsUL, C-UL, NYC
DatasheetTYCO TFP620

The critical point: glazing conditions

Protection is listed for specific glass types (heat-strengthened, tempered or ceramic) with set distances from mullions and a minimum flow of 20 GPM for 6 – 8 ft spacing or 15 GPM below 6 ft. No blinds or curtains between sprinkler and glass; not listed where intermediate horizontal mullions are present.

Installation steps

  1. Inspect before installing: never install a sprinkler whose bulb is cracked or has lost liquid.
  2. Install the sprinkler in its correct orientation (Window Pendent Vertical Sidewall) as shown in the datasheet — never reversed.
  3. Apply pipe-thread sealant to the threads, then hand-tighten the sprinkler.
  4. Finish with the specified wrench (W-Type 20) within 7 – 14 lb-ft (9.5 – 19.0 N·m). Higher torque can distort the inlet and cause leakage.

Common mistakes

  • Installing a sprinkler that was dropped, struck or slipped by the wrench. The datasheet requires any such sprinkler to be replaced.
  • Painting or coating sprinklers on site. Sprinklers must not be altered after leaving the factory; altered sprinklers are replaced.
  • Hanging objects from sprinklers, or cleaning them with anything other than a gentle feather duster.

Maintenance

Sprinklers that leak or show visible corrosion must be replaced, as must sprinklers exposed to corrosive products of combustion that cannot be fully cleaned. The owner is responsible for inspection, testing and maintenance to NFPA 25 and the authority having jurisdiction, preferably by a qualified inspection service. Before closing a main control valve for maintenance, obtain permission from the proper authorities and notify everyone affected.

Files and ordering

TYCO datasheet TFP620 and the available approval certificates are in the files section of this page. When ordering, state the model TY3488, temperature rating and finish. The datasheet lists the part numbers (P/N) for each combination.

How to order

Use the “Build your order” section on this page: add every model and quantity, then send the whole order by email or WhatsApp. It reaches us as a tidy PDF request sheet and we contact you with the quotation.

FAQ

What does TY3488 mean?

It is TYCO’s Sprinkler Identification Number (SIN). It identifies the exact model — orientation, K-factor and thread. The sprinkler is ordered by this number together with temperature rating and finish.

How do I choose the temperature rating?

From the highest expected ceiling temperature and the rating classes in the project’s governing standard, within the ratings available for this model in the datasheet.

Do all models in the series carry the same approvals?

Not always. The approvals table in datasheet TFP620 gives each model’s approvals by rating and finish, so check it when the project requires a specific approval.

What is the benefit of quick response?

The thermal element reacts faster, so the sprinkler operates earlier and limits heat and smoke spread; standards require it in some occupancies such as light hazard.

References

  • TYCO TFP620 — Series datasheet (attached)
  • NFPA 13 — Standard for the Installation of Sprinkler Systems
  • NFPA 25 — Inspection, Testing and Maintenance of Water-Based Fire Protection Systems
  • TYCO TFP700 — Installer warning for handling and installing sprinklers

This page is general information to help with selection and ordering, taken from the attached TYCO datasheet. Final design is set by the project’s approved designer; the project specification, the consultant’s drawings and the latest datasheet revision govern.