Skip to content
Exclusive agent of MECH products in Saudi Arabia
Store Request a quote

TYCO TY4811 Upright Sprinkler, K8.0, 1/2″ NPT — TY-L

Model TY4811

Brand
TYCO
Model
TY4811
Series
TY-L
Orientation
Upright
K-factor
8.0 gpm/psi½
Thread connection
1/2" NPT
Response
Standard Response
Coverage
Standard Coverage
Temperature ratings
74°C / 100°C / 138°C
Max. working pressure
175 psi (12.1 bar)
Approvals
UL · C-UL · FM · EAC
Datasheet
TFP110
Request a quote for this product
Or buy from the online store

The TYCO TY4811 is the upright model of the TY-L series, with a K 8.0 discharge coefficient and 1/2″ NPT thread, standard response and standard coverage, operated by a solder-type element. It is designed for light, ordinary and extra-hazard occupancies such as banks, hotels, shopping malls, factories, refineries and chemical plants. Installed above the pipe with the deflector facing up. For where the sprinkler sits in the whole system, see the complete guide to sprinkler systems in Saudi Arabia.

In short

  • Model (SIN): TY4811 — Upright.
  • Discharge coefficient K 8.0, 1/2″ NPT connection.
  • Solder-type element, standard response.
  • Temperature ratings in the datasheet: 74°C / 100°C / 138°C.
  • Maximum working pressure: 175 psi (12.1 bar).
  • Series approvals: UL, C-UL, FM, EAC. The approval of each model, finish and rating is in the approvals table of datasheet TFP110.
  • This model combines a 1/2″ thread with a K-factor greater than 5.6; NFPA 13 prohibits this in new construction, so it is for retrofit in existing systems only.

How this sprinkler works

A copper tube sealed by two stainless steel balls holds a fusible alloy. When the rated temperature is reached the alloy melts, the balls are forced toward each other and the tension mechanism releases, letting the sprinkler operate.

Installed above the pipe with the deflector facing up. Standard response is typically used for storage and industrial areas, per the project design.

Models in the series

Models in datasheet TFP110
SINOrientationK-factorThread
TY3111Upright5.61/2″ NPT
TY3211Pendent / Recessed Pendent5.61/2″ NPT
TY4111Upright8.03/4″ NPT
TY4811 — this modelUpright8.01/2″ NPT

Links to the other models are in the “Similar models” table below. The choice of model comes from the hydraulic calculation, hazard classification and installation method in the project design.

Application notes

  • A solder-type sprinkler rather than a bulb type; an intermediate-level version of the pendent is described in the datasheet.
  • Wax-coated sprinklers are tightened with an adjustable wrench taking care not to damage the wax; retouching with a heated rod is permitted only at initial installation.

Technical data

Technical data — TY4811 per TYCO datasheet TFP110
ItemValue
Model (SIN)TY4811
OrientationUpright
Discharge coefficientK 8.0 gpm/psi½ (115.2 L/min/bar½)
Thread1/2″ NPT
Element and responseSolder-type element — Standard Response
CoverageStandard Coverage
Temperature ratings74°C / 100°C / 138°C
Maximum working pressure175 psi (12.1 bar)
Installation torque7 – 14 lb-ft (9.5 – 19.0 N·m)
WrenchW-Type 9
EscutcheonRecessed pendent: Style 20 recessed escutcheon only
ApprovalsUL, C-UL, FM, EAC
DatasheetTYCO TFP110

The critical point: wrench and torque

Tighten only with the W-Type 9 wrench on the wrenching area, within the torque for its thread. Higher torque can distort the inlet and cause leakage or impairment.

A wax-coated 138°C sprinkler takes the same maximum ceiling temperature as the 100°C sprinkler, which is 65°C.

Installation steps

  1. Install the sprinkler in its correct orientation (Upright) as shown in the datasheet — never reversed.
  2. Apply pipe-thread sealant to the threads, then hand-tighten the sprinkler.
  3. Finish with the specified wrench (W-Type 9) within 7 – 14 lb-ft (9.5 – 19.0 N·m). Higher torque can distort the inlet and cause leakage.

Common mistakes

  • Using this 1/2″ model with a K-factor above 5.6 in a new building; it is for retrofit only.
  • Installing a sprinkler that was dropped, struck or slipped by the wrench. The datasheet requires any such sprinkler to be replaced.
  • Painting or coating sprinklers on site. Sprinklers must not be altered after leaving the factory; altered sprinklers are replaced.
  • Hanging objects from sprinklers, or cleaning them with anything other than a gentle feather duster.

Maintenance

Sprinklers that leak or show visible corrosion must be replaced, as must sprinklers exposed to corrosive products of combustion that cannot be fully cleaned. The owner is responsible for inspection, testing and maintenance to NFPA 25 and the authority having jurisdiction, preferably by a qualified inspection service. Before closing a main control valve for maintenance, obtain permission from the proper authorities and notify everyone affected.

Files and ordering

TYCO datasheet TFP110 and the available approval certificates are in the files section of this page. When ordering, state the model TY4811, temperature rating and finish, escutcheon. The datasheet lists the part numbers (P/N) for each combination.

How to order

Use the “Build your order” section on this page: add every model and quantity, then send the whole order by email or WhatsApp. It reaches us as a tidy PDF request sheet and we contact you with the quotation.

FAQ

What does TY4811 mean?

It is TYCO’s Sprinkler Identification Number (SIN). It identifies the exact model — orientation, K-factor and thread. The sprinkler is ordered by this number together with temperature rating and finish.

How do I choose the temperature rating?

From the highest expected ceiling temperature and the rating classes in the project’s governing standard, within the ratings available for this model in the datasheet.

Do all models in the series carry the same approvals?

Not always. The approvals table in datasheet TFP110 gives each model’s approvals by rating and finish, so check it when the project requires a specific approval.

References

  • TYCO TFP110 — Series datasheet (attached)
  • NFPA 13 — Standard for the Installation of Sprinkler Systems
  • NFPA 25 — Inspection, Testing and Maintenance of Water-Based Fire Protection Systems
  • TYCO TFP700 — Installer warning for handling and installing sprinklers

This page is general information to help with selection and ordering, taken from the attached TYCO datasheet. Final design is set by the project’s approved designer; the project specification, the consultant’s drawings and the latest datasheet revision govern.

Similar models

Same type — compare K-factor, response and approvals to pick the right one.

ProductModelKResponseApprovals
TYCO TY3111 Upright Sprinkler, K5.6, 1/2″ NPT — TY-L5.6Standard ResponseUL · C-UL · FM · EAC
TYCO TY3211 Pendent / Recessed Pendent Sprinkler, K5.6, 1/2″ NPT — TY-L5.6Standard ResponseUL · C-UL · FM · EAC
TYCO TY4111 Upright Sprinkler, K8.0, 3/4″ NPT — TY-L8.0Standard ResponseUL · C-UL · FM · EAC