Skip to content
Exclusive agent of MECH products in Saudi Arabia
Store Request a quote

TYCO TY7251 Pendent Sprinkler, K16.8, 3/4″ NPT — K17-231

Model TY7251

Brand
TYCO
Model
TY7251
Series
K17-231
Orientation
Pendent
K-factor
16.8 gpm/psi½
Thread connection
3/4" NPT
Response
Standard Response
Coverage
Standard Coverage
Temperature ratings
68 / 93 / 141 °C
Max. working pressure
175 psi (12.1 bar)
Approvals
UL · C-UL · FM (upright only) · NYC · EAC
Datasheet
TFP332
Request a quote for this product
Or buy from the online store

The TYCO TY7251 is the pendent model of the K17-231 series, with a K 16.8 discharge coefficient and 3/4″ NPT thread, standard response and standard coverage, operated by a glass bulb 5 mm. It is designed for high-piled storage and high-density applications, in lieu of K 8.0 or K 11.2 standard spray sprinklers. Installed hanging below the pipe with the deflector facing down. For where the sprinkler sits in the whole system, see the complete guide to sprinkler systems in Saudi Arabia.

In short

  • Model (SIN): TY7251 — Pendent.
  • Discharge coefficient K 16.8, 3/4″ NPT connection.
  • Glass bulb 5 mm, standard response.
  • Temperature ratings in the datasheet: 68 / 93 / 141 °C.
  • Maximum working pressure: 175 psi (12.1 bar).
  • Series approvals: UL, C-UL, FM (upright only), NYC, EAC. The approval of each model, finish and rating is in the approvals table of datasheet TFP332.
  • FM approval for this series is for the upright only; this pendent is UL and C-UL listed.

How this sprinkler works

The glass bulb contains a fluid that expands when exposed to heat. When the rated temperature is reached, the fluid expands enough to shatter the bulb, the sprinkler opens and the deflector spreads the water over the fire area.

Installed hanging below the pipe with the deflector facing down. Standard response is typically used for storage and industrial areas, per the project design.

Models in the series

Models in datasheet TFP332
SINOrientationK-factorThread
TY7151Upright16.83/4″ NPT
TY7251 — this modelPendent16.83/4″ NPT

Links to the other models are in the “Similar models” table below. The choice of model comes from the hydraulic calculation, hazard classification and installation method in the project design.

Application notes

  • K 16.8 gives very high flow at lower pressure. The datasheet requires a minimum deflector-to-top-of-storage clearance of 18 in. (457 mm).

Technical data

Technical data — TY7251 per TYCO datasheet TFP332
ItemValue
Model (SIN)TY7251
OrientationPendent
Discharge coefficientK 16.8 gpm/psi½ (241.9 L/min/bar½)
Thread3/4″ NPT
Element and responseGlass bulb 5 mm — Standard Response
CoverageStandard Coverage
Temperature ratings68 / 93 / 141 °C
Maximum working pressure175 psi (12.1 bar)
Installation torque10 – 20 lb-ft (13.4 – 26.8 N·m)
WrenchW-Type 8
ApprovalsUL, C-UL, FM (upright only), NYC, EAC
DatasheetTYCO TFP332

The critical point: clearance above storage

Keep at least 18 in. (457 mm) between the deflector and the top of storage, and tighten with the W-Type 8 wrench at 10 – 20 lb-ft.

Installation steps

  1. Inspect before installing: never install a sprinkler whose bulb is cracked or has lost liquid.
  2. Install the sprinkler in its correct orientation (Pendent) as shown in the datasheet — never reversed.
  3. Apply pipe-thread sealant to the threads, then hand-tighten the sprinkler.
  4. Finish with the specified wrench (W-Type 8) within 10 – 20 lb-ft (13.4 – 26.8 N·m). Higher torque can distort the inlet and cause leakage.

Common mistakes

  • Installing a sprinkler that was dropped, struck or slipped by the wrench. The datasheet requires any such sprinkler to be replaced.
  • Painting or coating sprinklers on site. Sprinklers must not be altered after leaving the factory; altered sprinklers are replaced.
  • Hanging objects from sprinklers, or cleaning them with anything other than a gentle feather duster.

Maintenance

Sprinklers that leak or show visible corrosion must be replaced, as must sprinklers exposed to corrosive products of combustion that cannot be fully cleaned. The owner is responsible for inspection, testing and maintenance to NFPA 25 and the authority having jurisdiction, preferably by a qualified inspection service. Before closing a main control valve for maintenance, obtain permission from the proper authorities and notify everyone affected.

Files and ordering

TYCO datasheet TFP332 and the available approval certificates are in the files section of this page. When ordering, state the model TY7251, temperature rating and finish. The datasheet lists the part numbers (P/N) for each combination.

How to order

Use the “Build your order” section on this page: add every model and quantity, then send the whole order by email or WhatsApp. It reaches us as a tidy PDF request sheet and we contact you with the quotation.

FAQ

What does TY7251 mean?

It is TYCO’s Sprinkler Identification Number (SIN). It identifies the exact model — orientation, K-factor and thread. The sprinkler is ordered by this number together with temperature rating and finish.

How do I choose the temperature rating?

From the highest expected ceiling temperature and the rating classes in the project’s governing standard, within the ratings available for this model in the datasheet.

Do all models in the series carry the same approvals?

Not always. The approvals table in datasheet TFP332 gives each model’s approvals by rating and finish, so check it when the project requires a specific approval.

References

  • TYCO TFP332 — Series datasheet (attached)
  • NFPA 13 — Standard for the Installation of Sprinkler Systems
  • NFPA 25 — Inspection, Testing and Maintenance of Water-Based Fire Protection Systems
  • TYCO TFP700 — Installer warning for handling and installing sprinklers

This page is general information to help with selection and ordering, taken from the attached TYCO datasheet. Final design is set by the project’s approved designer; the project specification, the consultant’s drawings and the latest datasheet revision govern.

Similar models

Same type — compare K-factor, response and approvals to pick the right one.

ProductModelKResponseApprovals
TYCO TY7151 Upright Sprinkler, K16.8, 3/4″ NPT — K17-23116.8Standard ResponseUL · C-UL · FM (upright only) · NYC · EAC