TYCO TY3251 Pendent / Recessed Pendent Sprinkler, K5.6, 1/2″ NPT — TY-B

Model TY3251

Brand
TYCO
Model
TY3251
Series
TY-B
Orientation
Pendent / Recessed Pendent
K-factor
5.6 gpm/psi½
Thread connection
1/2" NPT
Response
Standard Response
Coverage
Standard Coverage
Temperature ratings
57 / 68 / 79 / 93 / 141 / 182 °C
Max. working pressure
175 psi (12.1 bar); 250 psi (17.2 bar) under UL and C-UL (non-recessed)
Approvals
UL · C-UL · FM; LPCB / VdS for specific models
Datasheet
TFP151
Request a quote for this product
Or buy from the online store

The TYCO TY3251 is the pendent / recessed pendent model of the TY-B series, with a K 5.6 discharge coefficient and 1/2″ NPT thread, standard response and standard coverage, operated by a glass bulb 5 mm. It is designed for light, ordinary and extra-hazard occupancies such as banks, hotels, shopping malls, factories, refineries and chemical plants. Installed hanging below the pipe; it can also be recessed into a finished ceiling with its specified recessed escutcheon. For where the sprinkler sits in the whole system, see the complete guide to sprinkler systems in Saudi Arabia.

In short

  • Model (SIN): TY3251 — Pendent / Recessed Pendent.
  • Discharge coefficient K 5.6, 1/2″ NPT connection.
  • Glass bulb 5 mm, standard response.
  • Temperature ratings in the datasheet: 57 / 68 / 79 / 93 / 141 / 182 °C.
  • Maximum working pressure: 175 psi (12.1 bar); 250 psi (17.2 bar) under UL and C-UL (non-recessed).
  • Series approvals: UL, C-UL, FM; LPCB / VdS for specific models. The approval of each model, finish and rating is in the approvals table of datasheet TFP151.

How this sprinkler works

The glass bulb contains a fluid that expands when exposed to heat. When the rated temperature is reached, the fluid expands enough to shatter the bulb, the sprinkler opens and the deflector spreads the water over the fire area.

Installed hanging below the pipe; it can also be recessed into a finished ceiling with its specified recessed escutcheon. Standard response is typically used for storage and industrial areas, per the project design.

Models in the series

Models in datasheet TFP151
SINOrientationK-factorThread
TY3151Upright5.61/2″ NPT
TY3251 — this modelPendent / Recessed Pendent5.61/2″ NPT
TY4151Upright8.03/4″ NPT
TY4251Pendent / Recessed Pendent8.03/4″ NPT
TY4851Upright8.01/2″ NPT
TY4951Pendent8.01/2″ NPT

Links to the other models are in the “Similar models” table below. The choice of model comes from the hydraulic calculation, hazard classification and installation method in the project design.

Application notes

  • For in-rack use protected by solid shelves or horizontal barriers, the unshielded TY3151 / TY3251 / TY4151 / TY4251 are used; otherwise the intermediate-level versions in TFP351.
  • Corrosion-resistant finishes are available per the datasheet for corrosive atmospheres; the datasheet notes that corrosion tests do not represent every possible atmosphere, so suitability for the actual environment should be checked.

Technical data

Technical data — TY3251 per TYCO datasheet TFP151
ItemValue
Model (SIN)TY3251
OrientationPendent / Recessed Pendent
Discharge coefficientK 5.6 gpm/psi½ (80.6 L/min/bar½)
Thread1/2″ NPT
Element and responseGlass bulb 5 mm — Standard Response
CoverageStandard Coverage
Temperature ratings57 / 68 / 79 / 93 / 141 / 182 °C
Maximum working pressure175 psi (12.1 bar); 250 psi (17.2 bar) under UL and C-UL (non-recessed)
Installation torque7 – 14 lb-ft (9.5 – 19.0 N·m)
WrenchW-Type 6 (W-Type 7 for recessed)
EscutcheonRecessed pendent: Style 10 (1/2″) or Style 40 (3/4″)
ApprovalsUL, C-UL, FM; LPCB / VdS for specific models
DatasheetTYCO TFP151

The critical point: torque and the right wrench

Tighten only with the W-Type 6 wrench (W-Type 7 for recessed) on the wrench flats, never by the frame or deflector. Higher torque can distort the inlet.

Do not compensate for too little escutcheon adjustment by under- or over-tightening; readjust the sprinkler fitting instead.

Installation steps

  1. Inspect before installing: never install a sprinkler whose bulb is cracked or has lost liquid.
  2. Install the sprinkler in its correct orientation (Pendent / Recessed Pendent) as shown in the datasheet — never reversed.
  3. Apply pipe-thread sealant to the threads, then hand-tighten the sprinkler.
  4. Finish with the specified wrench (W-Type 6 (W-Type 7 for recessed)) within 7 – 14 lb-ft (9.5 – 19.0 N·m). Higher torque can distort the inlet and cause leakage.
  5. With an escutcheon, use only the specified one (Recessed pendent: Style 10 (1/2″) or Style 40 (3/4″)) and never compensate for adjustment by changing the torque.

Common mistakes

  • Compensating for too little recessed escutcheon adjustment by under- or over-tightening instead of readjusting the fitting.
  • Installing a sprinkler that was dropped, struck or slipped by the wrench. The datasheet requires any such sprinkler to be replaced.
  • Painting or coating sprinklers on site. Sprinklers must not be altered after leaving the factory; altered sprinklers are replaced.
  • Hanging objects from sprinklers, or cleaning them with anything other than a gentle feather duster.

Maintenance

Sprinklers that leak or show visible corrosion must be replaced, as must sprinklers exposed to corrosive products of combustion that cannot be fully cleaned. The owner is responsible for inspection, testing and maintenance to NFPA 25 and the authority having jurisdiction, preferably by a qualified inspection service. Before closing a main control valve for maintenance, obtain permission from the proper authorities and notify everyone affected.

Files and ordering

TYCO datasheet TFP151 and the available approval certificates are in the files section of this page. When ordering, state the model TY3251, temperature rating and finish, escutcheon. The datasheet lists the part numbers (P/N) for each combination.

How to order

Use the “Build your order” section on this page: add every model and quantity, then send the whole order by email or WhatsApp. It reaches us as a tidy PDF request sheet and we contact you with the quotation.

FAQ

What does TY3251 mean?

It is TYCO’s Sprinkler Identification Number (SIN). It identifies the exact model — orientation, K-factor and thread. The sprinkler is ordered by this number together with temperature rating and finish.

How do I choose the temperature rating?

From the highest expected ceiling temperature and the rating classes in the project’s governing standard, within the ratings available for this model in the datasheet.

Do all models in the series carry the same approvals?

Not always. The approvals table in datasheet TFP151 gives each model’s approvals by rating and finish, so check it when the project requires a specific approval.

References

  • TYCO TFP151 — Series datasheet (attached)
  • NFPA 13 — Standard for the Installation of Sprinkler Systems
  • NFPA 25 — Inspection, Testing and Maintenance of Water-Based Fire Protection Systems
  • TYCO TFP700 — Installer warning for handling and installing sprinklers

This page is general information to help with selection and ordering, taken from the attached TYCO datasheet. Final design is set by the project’s approved designer; the project specification, the consultant’s drawings and the latest datasheet revision govern.

Similar models

Same type — compare K-factor, response and approvals to pick the right one.

ProductModelKResponseApprovals
TYCO TY3151 Upright Sprinkler, K5.6, 1/2″ NPT — TY-B5.6Standard ResponseUL · C-UL · FM; LPCB / VdS for specific models
TYCO TY4151 Upright Sprinkler, K8.0, 3/4″ NPT — TY-B8.0Standard ResponseUL · C-UL · FM; LPCB / VdS for specific models
TYCO TY4251 Pendent / Recessed Pendent Sprinkler, K8.0, 3/4″ NPT — TY-B8.0Standard ResponseUL · C-UL · FM; LPCB / VdS for specific models
TYCO TY4851 Upright Sprinkler, K8.0, 1/2″ NPT — TY-B8.0Standard ResponseUL · C-UL · FM; LPCB / VdS for specific models
TYCO TY4951 Pendent Sprinkler, K8.0, 1/2″ NPT — TY-B8.0Standard ResponseUL · C-UL · FM; LPCB / VdS for specific models