Skip to content
Exclusive agent of MECH products in Saudi Arabia
Store Request a quote

TYCO TY3358 Dry Horizontal Sidewall Sprinkler, K5.6, 1″ NPT — DS-1 EC

Model TY3358

Brand
TYCO
Model
TY3358
Series
DS-1 EC
Orientation
Dry Horizontal Sidewall
K-factor
5.6 gpm/psi½
Thread connection
1" NPT
Response
Standard Response
Coverage
Extended Coverage
Temperature ratings
57 / 68 °C
Max. working pressure
175 psi (12.1 bar)
Approvals
UL · C-UL · NYC
Datasheet
TFP520
Request a quote for this product
Or buy from the online store

The TYCO TY3358 is the dry horizontal sidewall model of the DS-1 EC series, with a K 5.6 discharge coefficient and 1″ NPT thread, standard response and extended coverage, operated by a glass bulb. It is designed for horizontal piping extensions through a wall to protect an unheated area, in light hazard with extended coverage. A dry-type sprinkler installed horizontally through a wall into the unheated area. For where the sprinkler sits in the whole system, see the complete guide to sprinkler systems in Saudi Arabia.

In short

  • Model (SIN): TY3358 — Dry Horizontal Sidewall.
  • Discharge coefficient K 5.6, 1″ NPT connection.
  • Glass bulb, standard response.
  • Temperature ratings in the datasheet: 57 / 68 °C.
  • Maximum working pressure: 175 psi (12.1 bar).
  • Series approvals: UL, C-UL, NYC. The approval of each model, finish and rating is in the approvals table of datasheet TFP520.
  • Standard response, 5 mm bulb.

How this sprinkler works

The glass bulb contains a fluid that expands when exposed to heat. When the rated temperature is reached, the fluid expands enough to shatter the bulb, the sprinkler opens and the deflector spreads the water over the fire area.

In a dry-type sprinkler a plug with sealing assembly at the inlet keeps water out of the sprinkler barrel while in service. When the element operates, the seat is released and a spring drives the plug clear, so water enters and discharges. The barrel extending into the cold area therefore stays free of water.

A dry-type sprinkler installed horizontally through a wall into the unheated area. Standard response is typically used for storage and industrial areas, per the project design.

Models in the series

Models in datasheet TFP520
SINOrientationK-factorThread
TY3338Dry Horizontal Sidewall5.61″ NPT
TY3358 — this modelDry Horizontal Sidewall5.61″ NPT

Links to the other models are in the “Similar models” table below. The choice of model comes from the hydraulic calculation, hazard classification and installation method in the project design.

Application notes

  • Minimum spacing between sprinklers to prevent cold soldering is 14 ft (4.3 m).

Technical data

Technical data — TY3358 per TYCO datasheet TFP520
ItemValue
Model (SIN)TY3358
OrientationDry Horizontal Sidewall
Discharge coefficientK 5.6 gpm/psi½ (80.6 L/min/bar½)
Thread1″ NPT
Element and responseGlass bulb — Standard Response
CoverageExtended Coverage
Temperature ratings57 / 68 °C
Maximum working pressure175 psi (12.1 bar)
Installation torque20 – 30 lb-ft (26.8 – 40.2 N·m)
WrenchW-Type 7
ApprovalsUL, C-UL, NYC
DatasheetTYCO TFP520

The critical point: fitting and exposed length

A dry-type sprinkler must be installed only in the fittings listed in the datasheet’s Design Criteria. On wet systems the exposed barrel length in the warm area must meet the minimum in the table for the protected-area temperature.

Installation steps

  1. Inspect before installing: never install a sprinkler whose bulb is cracked or has lost liquid.
  2. Confirm the fitting is one of the types listed in the datasheet’s Design Criteria section.
  3. Install the sprinkler in its correct orientation (Dry Horizontal Sidewall) as shown in the datasheet — never reversed.
  4. Apply pipe-thread sealant to the threads, then hand-tighten the sprinkler.
  5. Finish with the specified wrench (W-Type 7) within 20 – 30 lb-ft (26.8 – 40.2 N·m). Higher torque can distort the inlet and cause leakage.

Common mistakes

  • Installing the dry sprinkler in an unlisted fitting, or with less than the minimum exposed length in the table, so water freezes inside the barrel.
  • Installing a sprinkler that was dropped, struck or slipped by the wrench. The datasheet requires any such sprinkler to be replaced.
  • Painting or coating sprinklers on site. Sprinklers must not be altered after leaving the factory; altered sprinklers are replaced.
  • Hanging objects from sprinklers, or cleaning them with anything other than a gentle feather duster.

Maintenance

Sprinklers that leak or show visible corrosion must be replaced, as must sprinklers exposed to corrosive products of combustion that cannot be fully cleaned. The owner is responsible for inspection, testing and maintenance to NFPA 25 and the authority having jurisdiction, preferably by a qualified inspection service. Before closing a main control valve for maintenance, obtain permission from the proper authorities and notify everyone affected.

Files and ordering

TYCO datasheet TFP520 and the available approval certificates are in the files section of this page. When ordering, state the model TY3358, temperature rating and finish, and the required length. The datasheet lists the part numbers (P/N) for each combination.

How to order

Use the “Build your order” section on this page: add every model and quantity, then send the whole order by email or WhatsApp. It reaches us as a tidy PDF request sheet and we contact you with the quotation.

FAQ

What does TY3358 mean?

It is TYCO’s Sprinkler Identification Number (SIN). It identifies the exact model — orientation, K-factor and thread. The sprinkler is ordered by this number together with temperature rating and finish.

How do I choose the temperature rating?

From the highest expected ceiling temperature and the rating classes in the project’s governing standard, within the ratings available for this model in the datasheet.

Do all models in the series carry the same approvals?

Not always. The approvals table in datasheet TFP520 gives each model’s approvals by rating and finish, so check it when the project requires a specific approval.

Why a dry-type sprinkler rather than a standard one?

The barrel extending into the cold area stays free of water until operation, so it cannot freeze, while the water stays in the heated part of the system.

References

  • TYCO TFP520 — Series datasheet (attached)
  • NFPA 13 — Standard for the Installation of Sprinkler Systems
  • NFPA 25 — Inspection, Testing and Maintenance of Water-Based Fire Protection Systems
  • TYCO TFP700 — Installer warning for handling and installing sprinklers

This page is general information to help with selection and ordering, taken from the attached TYCO datasheet. Final design is set by the project’s approved designer; the project specification, the consultant’s drawings and the latest datasheet revision govern.

Similar models

Same type — compare K-factor, response and approvals to pick the right one.

ProductModelKResponseApprovals
TYCO TY3338 Dry Horizontal Sidewall Sprinkler, K5.6, 1″ NPT — DS-1 EC5.6Quick ResponseUL · C-UL · NYC